West Control Solutions Pro-4 User Manual

Page 20

Advertising
background image

3.5.7 Optimization at the set-point for 3-point stepping controller

With 3-point stepping controllers, the pulse attempt can be made with or without

position feedback. Unless feedback is provided, the controller calculates the mo-

tor actuator position internally by varying an integrator with the adjusted actuator

travel time. For this reason, precise entry of the actuator travel time (tt), as time

between stops is highly important. Due to position simulation, the controller

knows whether an increased or reduced pulse must be output. After supply volta-

ge switch-on, position simulation is at 50%. When the motor actuator was varied

by the adjusted travel time in one go, internal calculation occurs, i.e. the position

corresponds to the simulation:

Simulation

actual position

Internal calculation

tt

Internal calculation always occurs, when the actuator was varied by travel time

tt in one go , independent of manual or automatic mode. When interrupting the

variation, internal calculation is cancelled. Unless internal calculation occurred

already after self-tuning start, it will occur automatically by closing the actuator

once.

Unless the positioning limits were reached within 10 hours, a significant deviati-

on between simulation and actual position may have occurred. In this case, the

controller would realize minor internal calculation, i.e. the actuator would be clo-

sed by 20 %, and re-opened by 20 % subsequently. As a result, the controller

knows that there is a 20% reserve for the attempt.

Operation

Self-tuning

20

KS 90-1 / KS 92-1