Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital

input di1/2/3, the è-key or the Ò-key.

Configuration, see page 37: ConF / LOGI / Err.r

g

If an alarm is still valid that means the cause of the alarm is not removed so far

(Err-LED blinks), then other saved alarms can not be acknowledged and deleted.

Self-tuning heating ( ADA.H) and cooling ( ADA.C) error status:

DAC function ( DAC) error status:

Operation

KS 90-1 / KS 92-1

15

Error list / Maintenance manager

Error

status

Description

Behaviour

0

No error

3

Faulty control action Re-configure controller (inverse i direct)

4

No response of process

variable

The control loop is perhaps not closed: check sensor, connections

and process

5

Low reversal point

Increase ( ADA.H) max. output limiting Y.Hi or decrease (

ADA.C) min. output limiting Y.Lo

6

Danger of exceeded

set-point (parameter

determined)

If necessary, increase (inverse) or reduce (direct) set-point

7

Output step change

too small (dy > 5%)

Increase ( ADA.H) max. output limiting Y.Hi or reduce (

ADA.C) min. output limiting Y.Lo

8

Set-point reserve too

small

Acknowledgment of this error message leads to switch-over to

automatic mode.If self-tuning shall be continued,

increase set-point (invers), reduce set-point (direct)

or decrease set-point range

(r PArA / SEtp / SP.LO and SP.Hi )

9

Impulse tuning failed The control loop is perhaps not closed: check sensor, connections

and process

Error status

Description

Behaviour

0

No error

3

Output is blocked

Check the drive for blockage

4

Wrong method of operation

Wrong phasing, defect motor capacitor

5

Fail at Yp measurement

Check the connection to the Yp input

6

Calibration error

Manual calibration necessary