Defined as status byte are – West Control Solutions KS 800 Profibus Interface Manual User Manual

Page 12

Advertising
background image

q

Module H (Multiplexing of all 64 variable processdata and parameterchannel)

No..

Descr.

R/W

FIX Point-Format

Rem.

Number of

Bytes

Value

Hex

COM PROFIBUS

Inputs

] 16

0 Unit_State, Digital_Outputs

R

4

13

32DE

A, F

1 IndexIN

Read

R

2

50

1AE

Write

2 Read Value

R

2

50

1AE

Outputs

] 16

3 Unit_Cntrl I, Unit_Cntrl II

W

4

23

32DA

B

4 IndexOUT

Read

W

2

60

1AA

Write

5 Write Value

W

2

60

1AA

In- /Outputs

6 Parameterchannel

R/W

8 / 8

F3

4AX

Operating principle (reading):

w

Enter the index number into ‘Index OUT’ (Read).

w

After the index number is mirror-inverted in ‘Index IN’ (Read), the read value is stored in

‘Read Value’ .

Operating principle (writing):

w

Enter the index number into ‘Index OUT’ (Write)

w

Enter the value to be written into ‘Write Value’.

w

After the index number is mirror-inverted in ‘Index IN’ (Write), the value was transmitted.

g

To ensure consistent data transmission, ‘Index OUT’ (Write) and ‘Write Value’ must have been updated

safely before a PROFIBUS data cycle. If this cannot be ensured, proceed as follows: ‘0’ in ‘Index OUT’

(Write), write the value to be transmitted into ‘Write Value’ and write the index number into ‘Index OUT’

(Write). With entry ‘0’ in ‘Index OUT’ (Read) / ‘Index OUT’ (Write), no data are transmitted.

3.1

Defined as status byte are:

Unit_State

MSB

LSB

D15 D14 D13

..

..

D2

D1

D0

Bit no.

Name

Allocation

Status ‘0’

Status ‘1’

D0

IN13

Digital input IN13 (ParNo)

off

on

D1

IN14

Digital input IN14 (Coff)

off

on

D2

IN15

Digital input IN15 (Leck)

off

on

D3

IN16

Digital input IN16 (w/w2)

off

on

D4

always ‘0’

D5

Dex

Changed ComRead or ComWrite data

no

yes

D6, D7

Always ‘0’

D8

Err1

Transmission error channel 1

no

yes

D9

Err2

Transmission error channel 2

no

yes

D10

Err3

Transmission error channel 3

no

yes

D11

Err4

Transmission error channel 4

no

yes

D12

Err5

Transmission error channel 5

no

yes

D13

Err6

Transmission error channel 6

no

yes

D14

Err7

Transmission error channel 7

no

yes

D15

Err8

Transmission error channel 8

no

yes

Process data

9499 040 50511

12

Advertising