West Control Solutions KS 800 Profibus Interface Manual User Manual

Page 14

Advertising
background image

Rem. E Unit_Contrl II

MSB

LSB

D31 D30 D29

...

...

D2

D1

D0

Bit no.

Name

Allocation

Status ‘0’

Status ‘1’

D0

OUT17

Forcing of output OUT17

off

on

D1

OUT18

Forcing of output OUT18

off

on

D2

OUT19

Forcing of output OUT19

off

on

D3

OstartG

Start optimizing all group controllers

no start

start

D4

OStopG

Forcing of output OUT5

no stop

stop

D5

Dval

Forcing of output OUT6

flank 0->1

D6- D15

always "0"

Rem. F Cntrl_x

MSB

LSB

D15 D14 D13

...

...

D2

D1

D0

Bit no.

Name

Allocation

Status ‘0’

Status ‘1’

D0

A/M

Automatic/manual switch-over

auto

manual

D1

Coff

Controller switched off

no

yes

D2

w/W2

w/W2 switch-over

w

W2

D3

We/w

External/internal switch-over

external

internal

D4

OStart

Start optimization

1)

no start

start

D5

OStop

Stop optimization

1)

no stop

stop

D6 .. D15

unused, always ‘0’

Rem. G Digital_Outputs

MSB

LSB

D15 D14 D13

...

...

D2

D1

D0

Bit-No.

Name

Allocation

Status ‘0’

Status ‘1’

D0

Y1_7

Y1-Output Channel 7

off

on

D1

Y2_7

Y2-Output Channel s 7

off

on

D2

Y1_6

Y1-Output Channel 6

off

on

D3

Y2_6

Y2-Output Channel 6

off

on

D4

Y1_5

Y1-Output Channel 5

off

on

D5

Y2_5

Y2-Output Channel 5

off

on

D6

Y1_4

Y1-Output Channel 4

off

on

D7

Y2_4

Y2-Output Channel 4

off

on

D8

Y1_3

Y1-Output Channel 3

off

on

D9

Y2_3

Y2-Output Channel 3

off

on

D10

Y1_2

Y1-Output Channel 2

off

on

D11

Y2_2

Y2-Output Channel 2

off

on

D12

Y1_1

Y1-Output Channel 1

off

on

D13

Y2_1

Y2-Output Channel 1

off

on

D14

Y1_0

Y1-Output Channel 0

off

on

D15

Y2_0

Y2-Output Channel 0

off

on

Process data

9499 040 50511

14

1) Signals are active only with change from 0 Ä 1. The signal must be available, until a change of Orun

(see Status_x) has occurred.
2)See chapter 3.3 page 15 "Disabling mechanism with changes".