West Control Solutions KS 800 Profibus Interface Manual User Manual

Page 17

Advertising
background image

3.5.2

General communication structure

For transmission of the parameters required for the function block protocol via an 8-byte data window, the

access is composed of three parts:

w

Order header with specification of code, FB no., fct. no., type and the following real and integer values.

Start telegram structure:

Byte 0 Byte 1 Byte 2 Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

ID

ID1

Code FB no. Fct._no.

Type

Numb.real values

Numb.integer values

w

n data blocks with the data to be transmitted

Data telegram structure:

Transmission of real data as fixedpoint and of integer values

Byte 0 Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

ID

Count

Integer

w

An end block provides the operation result

Structure of the end telegram:

Byte 0 Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

ID

Result

Signification of result

0

OK

4

NAK

The read or write operation is always started by the master. With the number of real and integer values ≠ 0, a

write service, otherwise, a read service is started.
The code determines the access type:

Code < 100, no multiple of 10

Ä

individual access

Code < 100, multiple of 10

Ä

tens block access

Code > 100

Ä

overall block access

3.5.3

Data write sequence

Start telegram:

Master sends: Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

0x10

ID1

Code

FB no. Fct._no. Type

Numb.real values

Numb.integer values

Controller

replies:

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

0x10

Data telegrams:

Master sends: Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 - 7 Controller replies: Byte 0 Byte 1 Byte 2 Byte 3

Byte 4 - 7

0x68 count

Value

0x68 count

Thereby, the first value is sent with Count = 1. For flow control, Count is reflected by KS800 (? once). The

values are transmitted in the order real - integer.
End telegram:

Master sends:

Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 - 7 Controller replies: Byte 0 Byte 1 Byte 2-3

Byte 4 - 7

0x16

0x16

Result

Process data

17