West Control Solutions KS 800 Profibus Interface Manual User Manual

Page 29

Advertising
background image

I/O connection

(function no.: 2)

Code Descr.

R/W Type

Description

Range Rem.

0

Block 1...2

R

Block

1

State_alarm_out R

ST1

Status alarm outputs

H

2

State_dio

R

ST1

Status digital inputs/outputs

I

20

Block 21...24

R

Block

21

SnOEMOpt

R

INT

Serialnumber OEM-Field

22

SnFabMonth

R

INT

Serialnumber Produktion month

23

SnCntHi

R

INT

Serialnumber Counter High

24

SncntLo

R

INT

Serialnumber Counter Low

30

Block 31...33

R

Block

31

Fdo1

R/W INT

Forced digital outputs: OUT1 ... OUT8

J

32

Fdo2

R/W INT

Forced digital outputs: OUT9 ... OUT16

K

33

Fdo3

R/W INT

Forced digital outputs: OUT17 ... OUT19

L

Rem. H State_alarm_out

MSB

LSB

D7

D6

D5

D4

D3

D2

D1

D0

Bit no.

Name

Allocation

Status ‘0’

Status ‘1’

D0

R1

Relay 1

off

on

D1

R2

Relay 2

off

on

D2

R3

Relay 3

off

on

D3

do1_12 AL Alarm outputshort circuit OUT1 ... OUT12

off

on

D4

HCscAL

Alarm message heating current short circuit

off

on

D5

‘0’

always ‘0’

D6

‘1’

always ‘1’

D7

Parity

Rem. I State_dio

MSB

LSB

D7

D6

D5

D4

D3

D2

D1

D0

Bit no.

Name

Allocation

Status ‘0’

Status ‘1’

D0

Par_Nr

Parameter set number

set 0

set 1

D1

w/w2

w/w2 switch-over

w

w2

D2

Coff

Controller off

off

on

D3

Leck

Leakage current

off

on

D4

‘0’

always ‘0’

D5

do13_16f

OUT13 ... OUT16 Fail

no

yes

D6

‘1’

always ‘1’

D7

Parity

Rem. J Data structure

Bit

15 14 13 12 11 10 9 8

7

6

5

4

3

2

1

0

Signification 0 0 0 0 0 0 0 0 OUT8 OUT7 OUT6 OUT5 OUT4 OUT3 OUT2 OUT1

Rem. K Data structure

Bit

15 14 13 12 11 10 9 8

7

6

5

4

3

2

1

0

Signification 0 0 0 0 0

0 0 0 OUT16 OUT15 OUT14 OUT13 OUT12 OUT11 OUT10 OUT9

Rem. L Data structure

Bit

15 14 13 12 11 10 9 8

7

6

5

4

3

2

1

0

Signification 0 0 0 0 0 0 0 0

0

0

0

0

0

OUT19 OUT18 OUT17

Function block protocol

29