CONTR (FB no.: 50 ... 57 Type no.: 91)

All data which concern the controller are grouped in function block ‘CONTR’. They are available once for

each controller channel.

Process data

General

(function no.: 0)

Code Descr.

R/W

Type

Description

Range

Rem.

00

Block

R

Block

Block access (1...9)

1

Status 1

R

ST1

Status 1

A

3

W

R

FP

Eff. set-point

4

X

R

FP

Eff. process value

5

Y

R

FP

Effective output value

6

xw

R

FP

Control deviation

13

Status Alarm x R

INT

Status x and Alarm x

B1

18

Type

R

INT

Type no. of function block

90

20

Block

R

Block

Block access (21...26)

21

Xeff

R

FP

Eff. process value

22

Yeff

R

FP

Effective output variable

23

HC

R

FP

Heating current measureement value

24

Unit_State

R

ICMP

Input values (di)

Ä page 12

25

Alarm_x

R

ICMP

Alarm values

Ä page 13

B2

26

Status_x

R

ICMP

Status information

Ä page 13

30

Block

R

Block

Block access (31...38)

33

A/M

R/W

INT

Automatic/manual switch-over

0..1

34

OStart

R/W

INT

Optimization start

0..1

35

We/i

R/W

INT

Wext/Wint switch-over

0..1

36

w/w2

R/W

INT

w/w2 switch-over

0..1

38

Coff

R/W

INT

Controller off/on

0..1

C

Rem. A Status1: (code 01)

MSB

LSB

D7

D6

D5

D4

D3

D2

D1

D0

Bit no.

Name

Allocation

Status ‘0’

Status ‘1’

D0

Y1

Switching output

off

on

D1

Y2

Switching output

off

on

D2

A/M

Auto/manual

auto

manual

D3

CFail

Controller status

ok

not ok

D4

Coff

Controller switched off

no

yes

D5

XFail

Sensor fail

no

yes

D6

‘1’

always ‘1’

D7

Parity

Rem. B1 Status_alarm_x: Code 13

MSB

LSB

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

Bit no.

Name

Allocation

Status ‘0’

Status ‘1’

D0

w/w2

w/w2 switch over

w

w2

D1

we/wi

extern/intern switch over

extern

intern

D2

w/wanf

Start-setpoint switch over

w

wanf

D3

Orun

Optimisation activ

no

yes

D4

A/M

Automatic/Manuel switch over

Auto

Man

D5

Coff

Controller off

no

yes

D6

Y1

Switchung output 1

off

on

D7

Y2

Switching output 2

off

on

D8

Lim HH

Alarm HH

off

on

D9

Lim H

Alarm H

off

on

D10

Lim L

Alarm L

off

on

D11

Lim LL

Alarm LL

off

on

D12

Fail

Alarm sensor fail

no

yes

D13

HCAl

Heating current alarm

off

on

D14

LoopAl

Loop alarm

off

on

D15

"0"

always "0"

Function block protocol