1general – West Control Solutions KS 800 Profibus Interface Manual User Manual

Page 5

Advertising
background image

General

5

9499 040 50511

1

General

The KS800 multi-temperature controller versions (9407-480-30001) are equipped with a PROFIBUS-DP

interface for transmission of process parameter and configuration data. Connection is via the 9-pole sub-D

connector socket. The serial communication interface permits connections to supervisory systems,

visualization tools, etc.
Another interface, which is always provided as standard, is the PC interface. This interface serves for

connecting an engineering tool, which runs on a PC.
Communication is according to the master/slave principle. KS800-DP is always slave.
Cable medium as well as physical and electrical interface proporties:

w

Network topologie

Linear bus with active bus termination at both ends. Stub lines are possible (dependent of cable type, a

maximum overall stub line length of 6,6m with 1,5Mbit/s and of 1,6m with 3-12Mbit/s is possible).

w

Transmission medium

screened, twisted 2-wire cable (Ä EN 50170 vol.2).

w

Baudrates and cable lengths (without repeater)

The maximum cable length is dependent of transmission rate.

The Baudrate is determined by the master configuration.

Automatic Baudrate

detection

Baudrate

Maximum cable length

9,6 / 19,2 / 93,75 kbit/s

1200 m

187,5 kbit/s

1000 m

500

kbit/s

400 m

1,5

Mbit/s

200 m

3 ... 12 Mbit/s

100m

w

Interface

RS485 connectable with sub-D connector (9-pole).

w

Address settings

Address setting is possible as follows:

- Adjustment via coding switches, range 00 ... 99, default 00

- adjustment via software, range 0 ... 126, default 126

With the coding switches set to ‘00’, the adjusted software address is valid.

A modified coding switch address is active only after switching on the supply voltage again.

w

32 instruments in one segment. Extension to 127 by means of a repeater is possible.

KS800 with PROFIBUS-DP interface offers many advantages with respect to handling and integration into a

PROFIBUS network.

w

Diagnosis and monitoring via COM-LED

LED off: error identification for ‘no bus access’ (so far not addressed by the master)

LED on: OK, cyclic data exchange running

LED blinks: (2Hz) Data exchange interrupted

LED blinks: (4Hz) PROFIBUS parameter setting and configuration error.

w

Particularities

Configurable process data modules

Direct input and output reading and writing

Output forcing

Easy connection to PLCs