West Control Solutions KS 800 Profibus Interface Manual User Manual

Page 41

Advertising
background image

5.2.7

ALARM (FB no.: 70 ... 77 Type no.: 46)

Function block ‘ALARM’ defines the overall alarm processing of the relevant controller. The data are

available once per controller.

Process data

General

(function no.: 0)

Code Descr.

R/W Type

Description

Range

Rem.

00

Block

R

Block

Block access (1 .. 3)

1

Status_Al1 R

ST1

Alarm status 1

A

2

Status_Al2 R

ST1

Heating current alarm

B

3

HC

R

FP

Heating current meas. value

18

Type

R

INT

Type no. of function block

46

Rem A Status_Al1

MSB

LSB

D7

D6

D5

D4

D3

D2

D1

D0

Bit no.

Name

Allocation

Status ‘0’

Status ‘1’

D0

Lim HH

Alarm HH

off

on

D1

Lim H

Alarm H

off

on

D2

Lim L

Alarm L

off

on

D3

Lim LL

Alarm LL

off

on

D4

Fail

Fail

no

yes

D5

‘0’

always ‘0’

D6

‘1’

always ‘1’

D7

Parity

Rem B Status_Al2

MSB

LSB

D7

D6

D5

D4

D3

D2

D1

D0

Bit no.

Name

Allocation

Status ‘0’

Status ‘1’

D0

HCAl

Heating current alarm channel

off

on

D1

LeckAl

Leakage current alarm channel

off

on

D2

LoopAl

Loop-alarm channel

off

on

D3

SSRAl

Short circuit alarm channel

off

on

D4

Fail_H

Fail-alarm H

off

on

D5

Fail_HH

Fail alarm HH

off

on

D6

‘1’

always ‘1’

D7

Parity

Function block protocol

41

9499 040 50511