3process data, Process data – West Control Solutions KS 800 Profibus Interface Manual User Manual

Page 8

Advertising
background image

3

Process data

During data transmission, distinction of process data to be transmitted cyclically and parameter /

configuration data to be transmitted acyclically is made. The I/O data field is structured modularly for

matching it to the requirements of the control task.

Selection of the process data module is via configuration tools of the master circuits (e.g. with Siemens S5

via COM PROFIBUS).
The following process data modules can be configured:

Process data

module A:

read (66 bytes)

1)

write

1)

(52 bytes)

without

parameter

channel

Instrument status, (process value, output value, status, ..) Instrument control, (set-point, output value, ...)

Process data

module B:

read (74 bytes)

1)

write

1)

(60 bytes)*

with

parameter

channel

Instrument status, (process value, output value, status, ..) Instrument control, (set-point, output value, ...)

Process data

module C:

only parameter channel

1)

(8/8 bytes)

Process data

module D:

read (74 Byte)

1)

write (60 Byte)

1)

with parameter

channel

Instrument status, (process value, output value,

status, ..)

Instrument control, (set-point, output value, ...)

Process data

module E:

read (116 Byte)

1)

write (116Byte)

1)

with parameter

channel

Instrument status, (52 variable process data)

Instrument control, (52 variable process data)

Process data

module F:

read (92 Byte)

1)

write (92 Byte)

1)

with parameter

channel

Instrument status, (40 variable process data)

Instrument control, (40 variable process data)

Process data

module G:

read (28 Byte)

1)

write (28 Byte)

1)

with parameter

channel

Instrument status, (8 variable process data)

Instrument control, (8 variable process data)

Process data

module H:

read (16 Byte)

1)

write (16 Byte)

1)

with parameter

channel

Instrument status, (multiplexing 64 variable

process data)

Instrument control, (multiplexing 64 variable process

data)

The parameter channel is used for sequential transmission of parameter and configuration data. The values to

be adjusted and data significations are given in the following tables:

For the process data modules (module E - H), the cyclical transmission data must be selected by means of

the ‘KS800’ engineering tool via General instrument settings r

Communication r

Bus data.

Max. 64 data for reading and 64 data for writing can be selected. Dependent of selected process data

module, the first 52 data (module E), the first 40 data (module F), the first 8 data (module H) or all

data are used (module G).

Process data

9499 040 50511

8

1) Number of required bytes in the I/O field