West Control Solutions KS 800 Profibus Interface Manual User Manual

Page 38

Advertising
background image

Rem. B2 Cntrl_x: (Code 39)

MSB

LSB

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

Bit no.

Name

Allocation

Status ‘0’

Status ‘1’

D0

A/M

Automat/Manuel

Auto

Manuel

D1

Coff

Switch the controller off

no

yes

D2

w/w2

w/w2 switch over

w

w2

D3

we/wi

wext/wint

wext

wint

D4

OStart

Start the optimisation

no start

start

D5

Ostop

Stop the optimisation

no stop

stop

D6...D15 "0"

Always "0"

Set-point

Set-point processing (function no.:1)

Code

Descr.

R/W

Type

Description

Range

Rem.

00

Block

R

Block

Block access (1, 3)

01

WState

R

ST1

Set-point status

B

03

Wint

R

FP

Effective internal set-point

30

Block

R

Block

Block access (31...32)

31

Wnvol

R/W

FP

Int. set-point, non-volatile

-999..9999

32

Wvol

R/W

FP

Int. set-point, volatile

-999..9999

Rem. C WState: (code 01)

MSB

LSB

D7

D6

D5

D4

D3

D2

D1

D0

Bit no. Name

Allocation

Status ‘0’

Status ‘1’

D0

w/w2

w/w2 switch-over

w

W2

D1

we/wi

wext/wint

wext

wint

D2

w/wanf

start-up set-point switch-over w

wanf

D3

GRW

Gradient function active

no

yes

D4

Weff_fail Error effective set-point

no

yes

D5

‘0’

always ‘0’

D6

‘1’

always ‘1’

D7

Parity

Output variable

Output variable processing(function no.:4)

Code Descr.

R/W Type

Description

Range

Rem.

30

Block

R

Block Block access (31, 35)

31

dYman R/W FP

Difference output variable

-210..210

32

Yman

R/W FP

Absolute output variable

-105..105

33

Yinc

R/W INT

Increment. output variable

0, 1

34

Ydec

R/W INT

Decrement. output variable

0, 1

35

Ygrw_ls R/W INT

Speed for incr./decr. output variable offset

0, 1

Tuning

Self-tuning(function no.:5)

Code Descr.

R/W Type

Description

Range

Rem.

00

Block

R

Block Block access (1, 3)

1

State_Tune1

R

ST1

Status Tuning

D

3

ParNeff

R

INT

Eff. parameter set number

0...1

30

Block

R

Block Block access (31...39)

31

ParNr

R/W INT

Parameter set number effective

0 .. 1

32

Tu1

R

FP

Delay time heating

0...9999 s

33

Vmax1

R

FP

Rate of increase heating

0,000...9,999 %/s

34

Kp1

R

FP

Process gain heating

0,000...9,999

35

MSG1

R

INT

Error code of self-tuning heating

0...8

36

Tu2

R

FP

Delay time cooling

0...9999 s

37

Vmax2

R

FP

Rate of increase cooling

0,000...9,999 %/s

38

Kp2

R

FP

Process gain cooling

0,000...9,999

39

MSG2

R

INT

Error code of self-tuning cooling

0...8

Function block protocol

9499 040 50511

38

Advertising