1 scope of delivery 6, Function module for simatic – West Control Solutions KS 800 Profibus Interface Manual User Manual

Page 46

Advertising
background image

6.2

Function module for SIMATIC

®

S7

The S7-FB handling principle corresponds to the S5 variant. When starting an order and as long as the order

is active, calling up the FB is indispensable.

Dependent of S7-CPU and DP-Master, the I/O handling is different. With a CPU315-2 DP with on-board DP

interface, SFC modules 14 and 15 must be used for consistent data transmission. SFC modules 14 and 15

copy the I/O areas into the marker or data module area. When using an external CP (CP 342-5 DP), the

relevant DP-SEND and DP-RECEIVE FBs at the cycle start and end must be called up.

The FB has an instance DB, which must also be specified with FB call.

6.2.1

Structure

The call parameters of the function module are:

Name

Type Description / function

A-start

Pointer Output word address area start (e.g. address data area ‘RECORD’ of SFC 15, Ax, y when using an

external CP). The DB no. must also be transmitted when specifying a data word (e.g. DB4.DBX0.0)

E-start

Pointer Input word address area start (e.g. address data area ‘RECORD’ of SFC 15, Ex, y when using an

external CP). The DB no. must also be transmitted when specifying a data word (e.g. DB4.DBX0.0)

DB-Para Pointer

Specification of data module with the parameter setting data. The entry comprises the data module

no. and the data word no. at which the parameter data start. Thereby,no offset needs being taken

into account. The data are interpreted as parameter data (useful data) by the specified address. The

DB must be specified in the following form e.g. DB6.DBX10.0

Service

WORD Service (Read/Write)

Code_nr

WORD Code

FB_nr

WORD Function block no. (channel addressing)

FKT_nr

WORD Function no.

Typ

WORD No function (always ‘0’)

Timeout DWORD Timeout value, is decremented with each call. With a value of = 1, the order is cancelled with error

message ‘timeout’.

DWLR

WORD Length of real values

DWLI

WORD Length of integer values

DWLC

WORD D.c. always ‘0’

ANZW

W

The current transmision status for the selected data area is given in the display word. The structure of

the display word is:

15 14 13 12 11

10

9

8

7

6

5

4

3

2

1

0

Timeout

(FB)

Service

faulty

NAK

(access

by

controller

not

accepted)

Parity

error

Timeout

internal

(controller)

Waiting

for

end

telegram

Service

(0=Read;

1=Write)

Reset

order

Waits

for

acknowledgement

Order

finished

with

error

Order

finished

without

error

Order

running

The function module reads or writes KS800 parameter/configuration data.

w

A-start, E-start

The parameter channel input addresses or output addresses are entered into these parameters. The

addresses are determined during configuration of the unit connected to the PROFIBUS (STEP 7 -

hardware configuration)

w

DB-Para

DB-Para is a pointer to the data module, into which read data are written or from which data are taken

when writing.

Function modules

9499 040 50511

46