4quick entrance – West Control Solutions KS 800 Profibus Interface Manual User Manual

Page 22

Advertising
background image

4

Quick entrance

The disk enclosed in the engineering set includes the GSD file, project examples for a SIMATIC

®

S5 / S7,

the type file and configuration examples for COM PROFIBUS. Communication with a KS800-DP can be

built up easily by means of the configuration and a project.

4.1

Quick entrance with S5

Test environment

The following components are required for the test set-up:

w

Programming unit (PG740 recommended)

w

Automation unit

-

S5-115U, S5-135U or S5-155U with IM 308-C

w

KS800-DP

w

Engineering set (order no. 9407 999 09x11)

w

Cable

-

PROFIBUS cable

automation unit / IM 308-C i KS800-DP

-

programming unit i automation unit

4.1.1

Example of a test environment:

A KS800-DP with address 5 is to be connected to an IM 308-C via PROFIBUS-DP. Process data module B

is selected (8 process data channels and parameter channel). Data shall be transmitted in fix point format.

The I/O addresses in the S5 start with 0 in the P area.

g

Before taking the test environment into operation, ensure that the automation units do not contain user

software (“initial clear”). The same applies to the IM 308-C memory card.

Procedure:

w

Establishing the communications

w

Instrument configuration

-

Adjust address 5 on KS800-DP (via coding switches or engineering tool) and connect it to the

network.

-

Activate bus termination resistors at the controller connector and at the (S5) PLC connector.

w

PROFIBUS network configuration

-

Insert the disk (engineering set) into programming unit.

-

Call up COM PROFIBUS and load example (A:\KS800dp\type\example\Demo308i.et2)

- Select the correct CPU type with IM308C.

-

If necessary, adapt addressings and DP network and transmit them to the DP master (Ä Fig.: ).

w

Load S5 program

-

Insert disk (engineering set) into the programming unit.

-

Call up STEP

®

5.

-

Load program example, e.g. (A:\KS800dp\s5_fb\example.fix\...)

-

If necesary, match the addresses for send / receive window (A-A/E-A in FB) and transmit them to

the automation unit.

-

Switch automation unit to run

Quick entrance

9499 040 50511

22