Proseries, 3 manage configuration sets, Sonic-pro – Blue-White Sonic-Pro Hybrid Ultrasonic Flowmeters User Manual

Page 30: 1 activate a configuration set

Advertising
background image

ENTER

Ç

ESC

È

Setup Root Menu

Manage Configuration Sets

ÊActivate a Configuration Set

Open a Saved Configuration Set

Create a New Configuration Set

Delete a Saved Configuration Set

5.3
Manage
Configuration
Sets

Under the Manage Configuration Sets
menu item, the user is offered actions to
manage these Sets in much the same way as
files on a computer.

Activate a Configuration Set allows the
user to apply a Configuration Set to the
flowmeter, which will then enter Run Mode
and operate according to the configuration
information in that Set plus the setting of
the motherboard measurement mode switch.

Open a Saved Configuration Set allows the user to inspect and edit a Configuration
Set, reset it to the Factory Configuration, save changes to it, save it to a different Set,
etc.
Create a New Configuration Set begins a fresh Configuration Set, starting from the
pre-set Factory Configuration.

Delete a Saved Configuration Set removes a Configuration Set from the flowmeter.

Similar to operating on files in a computer, the editing of a Configuration Set takes
place in a temporary location called the “Working” Set. This must be saved by the user,
either back to where it came from or to a different numbered Set, otherwise it will be lost
if the flowmeter loses power or the user escapes from Setup Mode.

Page 30

Sonic-Pro

Industries, Ltd.

Industries, Ltd.

ProSeries

by Blue-White Ind.

TM

On selecting this action, a list of the pre-saved Configuration Sets will be shown. The
user can select a Configuration Set using the and soft buttons and
press the ENTER soft button to activate that Set. The flowmeter then exits the Setup

5.3.1
Activate a
Configuration
Set

З

И

ENTER

ENTER

Ç

ESC

È

Setup Root Menu

Manage Configuration Sets

Activate a Configuration Set

Configuration Set #1

Ê

Configuration Set #3

Configuration Set #4

Ê

Mode to the Transducer Positioning
State
and eventually the Startup State
and then to the Run Mode where it will
perform flow measurement using the
configuration data of that Set.

The Setup Root Menu will return to the
screen without the activation of a
Configuration Set if the user fails to
supply a password (if required), or presses
the ESC soft button twice.

This action is similar to Activate a Saved Configuration Set in that the user is able to
select and open a valid Configuration Set. On pressing the ENTER soft button and
supplying a password if necessary, the selected Configuration Set will be loaded into
the Working Set and the Configuration Edit Menu will appear. From this screen, the
user can navigate to and edit configuration items.

On selecting this action, the pre-set Factory Configuration data will be loaded into the
Working Set and the Configuration Edit Menu will appear. The banner will read
New Configuration Set. From this screen, you can navigate to and edit configuration
items and save the configuration to a numbered Set.

Deleting a Configuration Set starts out the same as Activate a Saved
Configuration Set
. On pressing the ENTER soft button and supplying a password if
necessary, the Configuration Set number and data will be deleted. Note that new
configuration data can now be saved to that numbered set). If all Configuration Sets
are deleted, the flowmeter will operate according to the Factory Configuration.

5.3.2
Open a
Configuration
Set

5.3.3
Create a New
Configuration
Set
5.3.4
Delete a
Configuration
Set