0 transducer installation, Proseries, Sonic-pro – Blue-White Sonic-Pro Hybrid Ultrasonic Flowmeters User Manual

Page 40: 1 transducer piping system location, 2 transducer mounting mode for doppler measurement

Advertising
background image

Page 40

Sonic-Pro

Industries, Ltd.

Industries, Ltd.

ProSeries

by Blue-White Ind.

TM

6.1
Transducer
Piping System
Location

NO

NO

Air bubble

Sediment

OK

OK

OK

OK

NO

NO

Down flows

must have

back pressure

Pipe must be full

Air could be trapped

!

10 x D

5 x D

Flow
Direction

6.3
Transducer
Mounting
Mode for
Transit Time
Measurement

TRANSIT TIME MOUNTING MODES

DOPPLER MOUNTING MODE

All pipe types and sizes

Select a pipe location that provides a minimum straight length of pipe of at least 10
times the pipe’s nominal pipe size and mark a point that is at least 5 times the pipe
diameter downstream from the nearest pipe fitting. See section 1.6 for the minimum
straight pipe length requirements.

TRANSDUCER MOUNTING LOCATION

6.0 Transducer Installation

6.2
Transducer
Mounting
Mode for
Doppler
Measurement

“V” Mount Mode

Typically smaller pipe

sizes from 2” to 6”

diameter.

“Z” Mount Mode

Typically larger pipe

sizes from 4” to 100”

diameter.

The optional T-Track mounting system may be used for transducer installation. T-Track
installation is described in a separate manual.

V-MOUNT

T-TRACK MOUNTING SYSTEM

If the fluid contains little or no particles (up
to 10% maximum), operate the meter using
the Transit Time method to obtain the best
accuracy. Select “V” mounting mode when
possible. The “V” mounting mode allows the
greatest sound travel distance while
permitting good signal strength. Basic pipe
material and size general guidelines are
shown below.

If the fluid to be measured contains
particles, the meter should be operated
using the Doppler measurement method.
For Doppler operation, the transducers will
be mounted directly opposite each other as
shown below.

Z-MOUNT

T-TRACK MOUNTING SYSTEM