Pdu a, Pdu b, Pdms – HP 6400.8400 Enterprise Virtual Array User Manual

Page 22: Pdu a pdu b

Advertising
background image

Figure 17 Dual PDU—rear view

3. Main circuit breaker

1. PDU B

4. Circuit breakers

2. PDU A

PDU A

PDU A connects to AC PDM A1–A4.

A PDU A failure:

Disables the power distribution circuit

Removes power from from the left side of the rack

Disables disk enclosure PS 1

Disables the left power supplies in the controllers

PDU B

PDU B connects to AC PDM B1–B4.

A PDU B failure:

Disables the power distribution circuit

Removes power from the right side of the rack

Disables disk enclosure PS 2

Disables the right power supplies in the controllers

PDMs

Depending on the rack, there can be up to eight PDMs mounted in the rear of the rack:

The PDMs on the left vertical rail connect to PDU A

The PDMs on the right vertical rail connect to PDU B

Each PDM has seven AC receptacles. The PDMs distribute the AC power from the PDUs to the
enclosures. Two power sources exist for each controller pair and disk enclosure. If a PDU fails, the
system will remain operational.

CAUTION:

The AC power distribution within a rack ensures a balanced load to each PDU and

reduces the possibility of an overload condition. Changing the cabling to or from a PDM could
cause an overload condition. HP supports only the AC power distributions defined in this user
guide.

22

EVA6400/8400 hardware