Maximum Cable Resistance Calculation for the
Barrier (Vaisala Order Code: 210664)

Calculation of the maximum cable length from barrier to
transmitter:

If assuming that the operating voltage would be

 24 V, the maximum

acceptable voltage drop U

drop

in cables is:

U

drop

= U

S

- U

min

U

drop

= 14 V - 12 V = 2 V

We also know that:

I

out

= 20 mA

and that total resistance of the cable R

cabletot

is cable resistance R

cable

multiplied with the total maximum length of the cables l

max

:

R

cabletot

= R

cable

× l

max

General specifications of HMT360:

Supply voltage

U

in

= 24 V (12 ... 35 V)

Maximum current

I

out

= 20 mA

Minimum operating voltage for
HMT360

U

min

= 12 V (15 V with serial port)

Stahl 9001/51-280-091-141 (values taken from the specifications):

Rated operating voltage

U

N

= 20 ... 35 V

Transmitter supply voltage

U

S

= U

N

- 9.5 V, when

U

N

 23.5 V

or U

S

= 14 V, when U

N

 23.5 V

Maximum load

R

L

 350 

Cable resistance (as an example)

R

cable

= 0.085

/m/core (2 ×

0.085

/m/pair)