Aalborg Vortex Insertion User Manual

Page 10

Advertising
background image

5

3.3 Piping

Guidelines

To ensure the high accuracy of flow measurement specified on the identification
sheet, piping and installation instructions must be followed carefully.

A)

The pipe immediately up and down stream of the flow meter must be of
sufficient length, straight and free of obstructions. Refer to the piping
requirements chart for exact dimensions (Figure 3).

B) It is recommended that straightening vanes be used on all vortex meters,

but it is not necessary.

C) When the vortex meter is being used as a controller, it is recommended

that any regulating valve be located downstream of the flow meter.

D) Weld beads on the internal wall of the pipe before or after the flow meter

should be ground flush with the pipe wall before the meter is installed.

E) Proper style and proper size gaskets should always be used when

installing the flow meter.

F) The meter can be rotated around the pipe in any direction.

3.4

Temperature and Pressure Taps (Optional)

Installation of temperature and pressure transducers (if used) should be in
accordance with the manufacturer’s specifications.

A) The temperature transducer should be installed between 2.5 and 3.5

diameters from the downstream side of the wafer body. Consult the
factory for the exact dimensions, or refer to additional information at the
end of this manual.

B) The pressure transducer should be installed between 2.0 and 3.5

diameters from the upstream side of the wafer body. Consult the factory
for the exact dimensions.