Aalborg Vortex Insertion User Manual
Page 89
84
COMMAND
NAME
DESCRIPTION
NO.
COMMAND SYNT
A
X
COMMAND
ARGUMENT 1
ARGUMENT 2
ARGUMENT 3
ARGUMENT 4
RESPONSE
Pressure
Alarms**
Sets / reads the status of the
pressure alarms.
Note: High and Low limits have
to be entered in the Pa units.
High alarm value has to be
more than Low alarm value.
Alarm conditions:
Pressure > High Limit = H
Pressure. < Low Limit = L
Low < Press. < High = N
10
PA
H
(high press. limit)
<V
alue>
(0–Max.Press.)
P
A
H:<V
alue [P
A]>
L
(low press. limit)
<V
alue>
(0-Max.Press.)
P
A
L:<V
alue [Pa]>
A
(action delay in
seconds)
<V
alue> (0-3600
sec.)
P
AA:<V
alue [sec]>
E
(enable alarm)
PA
:E
D
(disable alarm)*
PA
:D
R
(read
current status)
P
A
R:N (no alarm)
P
A
R:H (high alarm)
P
A
R: L (low alarm)
S
(Read
current settings)
P
AS:M,L,H,D,B where:
M – mode (E/D)
L – Low settings (Pa)
H – High settings (Pa)
D – Action Delay (sec)
B – Latch mode (0-1)
B Block (Latch)
mode
<V
alue>
(0-disabled*)
(1-enabl’d )
P
A
B
:<
V
al
u
e>
w
h
er
e:
V
alue = 0 – 1