COMMAND

NAME

DESCRIPTION

NO.

COMMAND SYNT

A

X

COMMAND

ARGUMENT 1

ARGUMENT 2

ARGUMENT 3

ARGUMENT 4

RESPONSE

Pulse

Output

Sets and controls action of the

programmable Pulse Output

cir

cuitr

y.

NOTE: Unit/Pulse

value has to be entered:-for

V

o

lumetric flow conditions

in currently selected volume EU

-for Mass flow conditions

in currently selected mass EU

EU has to be not time based.

It is recommended to set the

unit/pulse value equal to the

maximum flow in the same

units per second. This will limit

the pulse to no faster than one

pulse ever

y second.

Example: Maximum flow rate:

1200 liter/min (1200 liter/min =

20 liters per second)

If Unit/Pulse is set to 20 liters

per pulse, the output will pulse

once ever

y second.

13

P

C (flow

configuration)

V

-volum. flow

M-mass flow

<V

alue>

(Unit/Pulse)

V

o

lumetric flow -

current

V

o

lumetric E.U.

Mass flow - cur-

rent mass EU

(example:

10 litr/pulse)

PCV

:<value>,<value>

Example:

PCV

:V

,10

Or

PCM:<value>,<value>

Example:

PCM:M,2.5

T (Pulse active

T

ime in ms)

<value>

[10 -13000 ms]

PT

:<value>

Example: PT

:1000

D (disable pulse

output)*

P:D

E (enable pulse

output)

P:E

Q (read current

pulse output

Queue value)

PQ:<value>

(number of pulses)

S (setting status)

PS:Mode,FlowConditions,

Unit/Pulse,PulseT

imeInter

val

Fluid

Density for

standard

conditions

Read and set Fluid Density for

standard conditions in g/cm3

NOTE: it is not measured

density

.

14

FD

(New Density

V

alue)

0.0001

Density

10.0 g/cm3

FD:<value>

Example:

FD:1.293

No Argument

(Returns Current

Density in g/cm3)

FD:<value>

Example:

FD:1.293