Myron L 729II User Manual

Page 18

Advertising
background image

14

c.

Connect to your own alarm or ?

Use the following as guidelines.

Connector is a standard 2 wire Methode* style

connector. Connector with 8” wires, part #RAH, is

available from the Myron L Company.

Ensure your requirements do not exceed the 24VDC

Unregulated 30mA maximum.

Ensure the polarity is correct (RED is positive), see

figure V.A.1.

Attach wires to RA.

Attach connector to controller connector (RA) per figure

V.A.1.

*Methode is registered trademark of Methode Electronics, Inc.

5. ALARM/CONTROL RELAY CONNECTIONS

Myron L Company Monitor/controllers are equipped with a

“Dry Contact” relay which is designed to energize/de-energize

when the set point is crossed. (See section IV.C.3 for set point

adjustment procedure) The relay energizes on increasing or

decreasing readings as set by the user, see section IV.C.1.

When energized (above set point), the Common (COM) will

disconnect from the Normally Closed (NC) contact and connect

to the Normally Open (NO) contact. Devices may be operated

using either the Normally Open contact or Normally Closed

contact; or both relay contacts may be used to control two

devices of the same voltage.

NOTE: A flow switch may be installed (electrically connected)

utilizing one of two convenient methods; the 3S connection, see

figure II.E.2, (remove jumper and connect flow switch across

terminals - 8” harness (RAH) available from the

Myron L Company), or in-line with either relay connection,

see figure II.E.6 or II.E.7.

WARNING: CONNECTING BOTH POWER SOURCE

LEADS TO THE RELAY TERMINAL BLOCK CONNECTORS

WILL DAMAGE THE CIRCUIT BOARD AND MAY CAUSE

PERSONAL INJURY.

1. Place the user supplied Alarm relay interface cable and

watertight cable restraint into the enclosure’s

appropriate access hole. Skip for OEM.

2. Neatly connect the relay interface cable wires to the

Monitor/controller’s terminal block connectors, see

figures II.E.1, II.E.6 or II.E.7.

CAUTION: The connectors require only a small screwdriver or

a pen to push on the release levers. The release levers may

be broken or damaged if not pushed straight toward the circuit

board. DO NOT push the release levers sideways.

The easiest method of connecting the relay is shown in figures

II.E.1, and II.E.6. These show how the dry contact relay can use

incoming power to activate a controlled device (alarm, solenoid

valve, etc.) of 10 amps or less.

For 24 VAC applications, the Myron L Company offers a 115

VAC to 24 VAC transformer, Model #VR, see figure II.E.7. Other

voltages must be user-supplied.

6. CONNECTING DISPLAY HARNESS TO DISPLAY

If the installation required the removal of the display harness

from the display (OEM installation requires connection), the

following procedure will ensure it is reinstalled without damaging

the display.

WARNING: THE DISPLAY WILL BE IRREPARABLY

DAMAGED IF THE HARNESS IS INSTALLED UPSIDE-DOWN

OR MISALIGNED. THE HARNESS MUST BE INSTALLED AS

SHOWN IN FIGURE II.E.8.

1. Grasp connector and align wires DOWN on display or

with the small edge of the display as shown in figure

II.E.8.

2. Press connector onto display pins. Ensure pins are

aligned or they may become bent. Wiggle connector

slightly “end to end” if necessary.

DEVICE

TO BE

CONTROLLED

POWER

SOURCE

MONITOR / CONTROLLER

CIRCUIT BOARD

COM

NO

CM

NO

NC

RELAY

RELAY

TERMINAL BLOCK

OPT.

FLOW

SWITCH

X

DEVICE

TO BE

CONTROLLED

COM

NO

115VAC

POWER

SOURCE

CM

NO

NC

RELAY

VR

RELAY

TERMINAL BLOCK

115 to 24VAC

TRANSFORMER

MONITOR/CONTROLLER

CIRCUIT BOARD

OPT.

FLOW

SWITCH

X

DISPLAY CONNECTION

DISPLAY

HARNESS

DISPLAY

Figure II.E.6

PANEL MOUNTED DISPLAY

REAR VIEW

Figure II.E.8

Figure II.E.7

Advertising
This manual is related to the following products: