Bryant 582A User Manual

Page 16

Advertising
background image

Fig. 15—208/230-1-60 Wiring Diagram, Units 582A and 583A

C00057

COOLING FAN LOGIC

ENERGIZED DE-ENERGIZED

ENERGIZED DE-ENERGIZED

HEATING FAN LOGIC

FIELD

SUPPLY

EQUIP_GND

W15 YEL

W14 BLK

PRIMARY

230V

11

21

13

23

C

W16 YEL

W43 BLK

C

BLK

YEL

BRN

CAP 2

C

R

S

W8 BLK

W7 YEL

RED

YEL

BRN/WHT

OR YEL

BRN

V10

YEL

BRN

CAP 1

CAP 3

OFM

COMP

IFM

IDM

(SEE NOTE #4)

GRN-YEL

W24 YEL

W50 V10

QT

QT

W46 BRN

SECONDARY

24V

TRAN1

1

1

230

C

24V

COM

0

G

T

G

0

W

T

W

T+30

T+30

BR

45

BR

RC

RH

B

OFF
HEAT
AUTO

COOL

THI

AHA

WI

OFF
HEAT
AUTO

YI

TCI

COOL

AUTO

FAN
SW

FIELD-THERMOSTAT

ON

G

W13 BLK

24V SPLICE BOX

W19 WHT

W20 GRN

W21 RED

L1

CM

BM

L2

L2

L2

J2

IFC

W

G

R

CR

BR

W39 RED

IGC

RS

RS

LS

LS

CS

CS

GV

GV

CR

BR

GVR

FAN

LOGIC

SAFETY

LOGIC

5 AMP

FU

RT

BLU

BLU

V10

V10

GVR

W35 GRA

MGV

W34 BRN

FLAME SEN

YEL

BRN

W41 GRN-YEL

W32 BRN

W46 BRN

GRN-YEL

W32 BRN

W30 BRN

W33 YEL

GROUNDED
TRU STANDOFF

HS

HV

TRAN

FS

C

C

YEL

RS

LS1

1

3

C1

C2

C_

W30 BRN

COMMON

200

W44 RED

1

2

1 2 3

LS2

1

3

V10

SEE NOTE #5

POWER

SCHEMATIC
208/230-1-60

W54 YEL

1

3

W6 YEL

H

F

W9 BLU

YEL

W61 YEL

ST

W59 BLU

(582A ONLY)

UNIT COMPONENT ARRANGEMENT

GAS SECTION

OUTDOOR FAN
SECTION

COMPRESSOR
SECTION

INDOOR FAN
SECTION

CONTROL BOX

24V
SPLICE BOX

EQUIP
GND

OFM

TRAN

CAP 1

LS1

IFM

CAP3

IGC

CAP 2

HC F

23

21

C

13

11

COMP

C

S

R

IDM

HS

MGV
1 2

1

RS

FS

LS2

CAP 1

LARGE CHASSIS LOC

NOTES:
1. If any of the original wires furnished are replaced, they must be

replaced with type 90 degree C wire or its equivalent.

2. See price pages for thermostat and subbases.
3. Use 75 degree C copper conductors for field installation.
4. For high speed IFM, disconnect RED wire from IGC terminal BM

and connect BLK wire from IFM. For medium speed, disconnect
RED wire from IGC terminal BM and connect BLU wire from IFM.

5. Models 4BGX024-036 have LS1 and LS2 wired in series. Models

48GX042-060 have LS1 only.

DISCONNECT
PER NEC

AHA

– Adjustable Heat

Anticipator

BR

– Blower Relay

C

– Contactor

CAP

– Capacitor

COMP – Compressor Motor
CR

– Combustion Relay

CS

– Centrifugal Switch

EQUIP – Equipment
FS

– Flame Sensor

FU

– Fuse

GND

– Ground

GV

– Gas Valve

GVR

– Gas Valve Relay

HS

– Hall Effect Sensor

HV

– High Voltage

TRAN – Transformer
I

– Ignitor

IDM

– Induced-Draft Motor

IFC

– Indoor-Fan Contactor

IFM

– Indoor-Fan Motor

IGC

– Integrated Gas Unit

Controller

L1

– Line

LS

– Limit Switch

LS1

– Limit Switch

MGV

– Main Gas Valve

NEC

– National Electrical

Code

OFM

– Outdoor-Fan Motor

QT

– Quadruple Terminal

RS

– Rollout Switch

SEN

– Sensor

SW

– Switch

TRAN – Transformer

LEGEND

Field Splice

Terminal (Marked)

Terminal (Unmarked)

Splice

Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or
Optional Wiring
To Indicate Common
Potential Only, Not
to Represent Wiring

—16—