Fig. 3—582A048-060 and 583A042-060 Unit Dimensions

UNIT

ELECTRICAL CHARACTERISTICS

UNIT WEIGHT

UNIT HEIGHT IN. (MM)

A

CENTER OF GRAVITY

IN. (MM)

lb

kg

X

Y

Z

582A048090/115/130

208-230/1/60, 208/230-3-60, 460-3-60

415

188.6

38.98 (990.2)

22 (558.5)

16 (406.4)

17 (432.0)

582A060090/115/130

208/230-1-60, 208/230-3-60, 460-3-60

450

204.5

38.98 (990.2)

22 (558.5)

16 (406.4)

17 (432.0)

583A042060/090

208/230-1-60, 208/230-3-60, 460-3-60

382

173.3

38.98 (990.2)

23.0 (584.2)

16.3 (412.8)

16.6 (421.6)

583A048090/115/130

208/230-1-60, 208/230-3-60, 460-3-60

421

191.0

38.98 (990.2)

21.5 (546.1)

16.6 (422.1)

18.0 (457.2)

583A060090/115/130

208/230-1-60, 208/230-3-60, 460-3-60

468

212.3

42.98 (1091.1)

23.5 (596.9)

16.3 (412.8)

17.6 (447.0)

C00056

REQUIRED CLEARANCE FOR OPERATION AND SERVICING

INCHES [mm]

EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]
POWER ENTRY SIDE....................................................................36.00 [914.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]
DUCT PANEL .................................................................................12.00 [304.8] *

*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.

REQUIRED CLEARANCE TO COMBUSTIBLE MATL.

INCHES [mm]

TOP OF UNIT ...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT .............................................................................0.50 [12.7]
FLUE PANEL ....................................................................................36.00 [914.4]

NEC. REQUIRED CLEARANCES.

INCHES [mm]

BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]

LEGEND
CG - Center of Gravity
COND - Condensor
EVAP - Evaporator
NEC - National Electrical Code
REQ’D - Required

NOTE: Dimensions are in in. [mm]