Bryant 582A User Manual

Page 21

Advertising
background image

3. Start unit in Cooling mode and let unit run until system

pressures stabilize.

4. Measure and record the following:

a. Outdoor ambient-air temperature (°F db).

b. Evaporator inlet-air temperature (°F wb).

c. Suction-tube temperature (°F) at low-side service fitting.

d. Suction (low-side) pressure (psig).

5. Using “Cooling Charging Charts,” compare outdoor-air

temperature (°F db) with the suction line pressure (psig) to
determine desired system operating suction line temperature
(See Fig. 18–30).

6. Compare actual suction-tube temperature with desired

suction-tube temperature. Using a tolerance of ± 3°F, add
refrigerant if actual temperature is more than 3°F higher
than proper suction-tube temperature, or remove refrigerant
if actual temperature is more than 3°F lower than required
suction-tube temperature.

NOTE:

If the problem causing the inaccurate readings is a

refrigerant leak, refer to the Check for Refrigerant Leaks section.

C.

INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS

CAUTION:

For cooling operation, the recommended

airflow is 350 to 450 cfm for each 12,000 Btuh of rated
cooling capacity. For heating operation, the airflow must
produce a temperature rise that falls within the range
stamped on the unit rating plate.

Table 7 shows the temperature rise at various airflow rates. Tables
11 and 13 show both heating and cooling airflows at various
external static pressures. Refer to these tables to determine the
airflow for the system being installed (See Tables 14 and 15 for
wet coil pressure drop).

NOTE:

Be sure that all supply- and return-air grilles are open,

free from obstructions, and adjusted properly.

WARNING:

Before changing blower speed, shut off gas

supply. Then disconnect electrical power to the unit and
install lockout tag. Electrical shock or explosion can
cause serious injury or death.

Airflow can be changed by changing the lead connections of the
blower motor.
Unit 582A two- or three-speed motors (except size 030) are factory
wired for low speed operation. Unit 582A030 is factory wired for
medium speed.
All 583A units are factory wired for low speed and may need to be
wired for medium or high speed in the field.

FOR 208/230V

For color coding on the 208/230V motor leads, see Table 9.

To change the speed of the blower motor (BM), remove the fan
motor speed leg lead from the blower relay (BR). This wire is
attached to terminal BM of the integrated gas control (IGC) board
for single- and 3-phase units. To change the speed, remove and
replace with lead for desired blower motor speed. Insulate the
removed lead to avoid contact with chassis parts.

FOR 460-V GE MOTORS

For color coding on the 460-v GE motor leads, see Table 10.

To change the speed of the blower motor (BM), remove fan motor
speed lead from the blower relay (BR) and replace with the lead
for the desired blower motor speed. The motor speed lead is
attached to terminal BM of the integrated gas control (IGC) board.
For low and medium speeds, black must be connected to the
jumper wire. Insulate removed lead end to avoid contact with
chassis parts.
To select high speed on 460-v GE motors, separate
the black (female quick connect – QC – from the jumper lead
(male quick connect – QC) and connect the black lead to the BR.
Insulate the jumper to avoid contact with any chassis parts.

D.

COOLING SEQUENCE OF OPERATION

With the room thermostat SYSTEM switch in the COOL position
and the FAN switch in the AUTO. position, the cooling sequence
of operation is as follows:

1. When the room temperature rises to a point that is slightly

above the cooling control setting of the thermostat, the
thermostat completes the circuit between thermostat termi-
nal R to terminals Y and G. These completed circuits
through the thermostat:

2. The normally open contacts of energized contactor (C)

close and complete the circuit through compressor motor
(COMP) to condenser (outdoor) fan motor (OFM). Both
motors start instantly.

3. The set of normally open contacts of energized relay BM

close and complete the circuit through evaporator blower
(indoor) fan motor (IFM).

NOTE:

Once the compressor has started and then stopped, it

should not be started again until 5 minutes have elapsed. The
cooling cycle remains “on” until the room temperature drops to a
point that is slightly below the cooling control setting of the room
thermostat. At this point, the thermostat “breaks” the circuit
between thermostat terminal R to terminals Y and G. These open
circuits deenergize contactor coil C. The condenser and compres-
sor motors stop. After a 30-sec. delay, the blower motor stops. The
unit is in a “standby” condition, waiting for the next “call for
cooling” from the room thermostat.

MAINTENANCE

To ensure continuing high performance and to minimize the
possibility of premature equipment failure, periodic maintenance
must be performed on this equipment. This combination
heating/cooling unit should be inspected at least once each year by
a qualified service person. To troubleshoot cooling or heating of
units, refer to Tables 16–18.

NOTE:

Consult your local dealer about the availability of a

maintenance contract.

TABLE 9–COLOR CODING FOR 208/230-V MOTOR

LEADS

3-SPEED

2-SPEED

black = high speed

black = high speed

blue = medium speed

red = low speed

red = low speed

TABLE 10–COLOR CODING FOR 460-V GE MOTOR

LEADS

3-SPEED

2–SPEED

black = high speed

black = high speed

violet = jumper

blue = jumper

orange = medium speed

red = low speed

red = low speed

—21—

Advertising