TABLE 16—TROUBLESHOOTING GUIDE—COOLING

SYMPTOM

CAUSE

REMEDY

Compressor and condenser fan
will not start.

Power Failure

Call power company.

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker.

Defective thermostat, contactor, transformer, or control relay

Replace component.

Insufficient line voltage

Determine cause and correct.

Incorrect or faulty wiring

Check wiring diagram and rewire correctly.

Thermostat setting too high

Lower thermostat setting below room temperature.

Compressor will not
start but condenser
fan runs.

Faulty wiring or loose connections in compressor circuit

Check wiring and repair or replace.

Compressor motor burned out, seized, or internal
overload open

Determine cause
Replace compressor.

Defective run/start capacitor, overload, start relay

Determine cause and replace.

One leg of 3-phase power dead

Replace fuse or reset circuit breaker.
Determine cause.

Three-phase scroll compressor
(582A048 and 583A030-060 only)
makes excessive noise, and there may
be a low pressure differential.

Scroll compressor is rotating in the wrong direction

Correct the direction of rotation by reversing the
3-phase power leads to the unit. Shut down unit
to allow pressures to equalize.

Compressor cycles (other than
normally satisfying thermostat).

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and recharge to
capacities shown on nameplate.

Defective compressor

Replace and determine cause.

Insufficient line voltage

Determine cause and correct.

Blocked condenser

Determine cause and correct.

Defective run/start capacitor, overload or start relay

Determine cause and replace.

Defective thermostat

Replace thermostat.

Faulty condenser-fan motor or capacitor

Replace.

Restriction in refrigerant system

Locate restriction and remove.

Compressor operates continuously.

Dirty air filter

Replace filter.

Unit undersized for load

Decrease load or increase unit size.

Thermostat set too low

Reset thermostat.

Low refrigerant charge

Locate leak, repair, and recharge.

Leaking valves in compressor

Replace compressor.

Air in system

Recover refrigerant, evacuate system, and recharge.

Condenser coil dirty or restricted

Clean coil or remove restriction .

Excessive head pressure.

Dirty air filter

Replace filter.

Dirty condenser coil

Clean coil.

Refrigerant overcharged

Recover excess refrigerant.

Air in system

Recover refrigerant, evacuate system, and recharge.

Condenser air restricted or air short-cycling

Determine cause and correct.

Head pressure too low.

Low refrigerant charge

Check for leaks, repair, and recharge.

Compressor valves leaking

Replace compressor.

Restriction in liquid tube

Remove restriction.

Excessive suction pressure.

High heat load

Check for source and eliminate.

Compressor valves leaking

Replace compressor.

Refrigerant overcharged

Recover excess refrigerant.

Suction pressure too low.

Dirty air filter

Replace Filter.

Low refrigerant charge

Check for leaks, repair, and recharge.

Metering device or low side restricted

Remove source of restriction.

Insufficient evaporator airflow

Increase air quantity. Check filter — replace if necessary.

Temperature too low in conditioned area

Reset thermostat.

Outdoor ambient below 40°F

Install low-ambient kit .

Field-installed filter-drier restricted

Replace.