Bryant 582A User Manual

Page 29

Advertising
background image

3. Inspect the fan blades for cracks or bends.

4. If fan needs to be removed, loosen the setscrew and slide

the fan off the motor shaft.

5. When replacing fan blade, position blade so the hub is 1/8

in. away from the motor end (1/8 in. of motor shaft will be
visible. See Fig. 12).

6. Ensure that setscrew engages the flat area on the motor shaft

when tightening.

7. Replace grille.

J.

ELECTRICAL CONTROLS AND WIRING

Inspect and check the electrical controls and wiring annually. Be
sure to turn off the gas supply, and then the electrical power to the
unit.

Remove access panel to locate all the electrical controls and
wiring. Check all electrical connections for tightness. Tighten all
screw connections. If any smoky or burned connections are
noticed, disassemble the connection, clean all the parts, restrip the
wire end and reassemble the connection properly and securely.

After inspecting the electrical controls and wiring, replace the
access panel. Start the unit, and observe at least one complete
heating cycle and one complete cooling cycle to ensure proper
operation. If discrepancies are observed in either or both operating
cycles, or if a suspected malfunction has occurred, check each
electrical component with the proper electrical instrumentation.
Refer to the unit wiring label when making these checkouts.

NOTE:

Refer to the heating and/or cooling sequence of operation

in this publication as an aid in determining proper control
operation

K.

REFRIGERANT CIRCUIT

Annually inspect all refrigerant tubing connections and the unit
base for oil accumulations. Detecting oil generally indicates a
refrigerant leak.

WARNING:

System under pressure. Relieve pressure

and recover all refrigerant before system repair or final
unit disposal to avoid serious injury or death. Use all
service ports and open all flow-control devices, including
solenoid valves.

If oil is detected or if low cooling performance is suspected,
leak-test all refrigerant tubing using an electronic leak-detector,
halide torch, or liquid-soap solution. If a refrigerant leak is
detected, refer to the Check for Refrigerant Leaks section.

If no refrigerant leaks are found and low cooling performance is
suspected, refer to the Checking and Adjusting Refrigerant Charge
section.

L.

GAS INPUT

The gas input does not require checking unless improper heating
performance is suspected. If a problem exists, refer to the Start-Up
section.

M.

EVAPORATOR AIRFLOW

The heating and/or cooling airflow does not require checking
unless improper performance is suspected. If a problem exists, be
sure that all supply- and return-air grilles are open and free from
obstructions, and that the air filter is clean.
When necessary, refer
to the Indoor Airflow and Airflow Adjustments section to check the
system airflow.

N.

METERING DEVICE — ACUTROL DEVICE

This metering device is a fixed orifice and is located in the header
to the evaporator coil.

O.

LIQUID LINE STRAINER

The liquid line strainer (to protect metering device) is made of wire
mesh and located in the liquid line on the inlet side of the metering
device.

TROUBLESHOOTING

Use the Troubleshooting Guides (See Tables 16–18) if problems
occur with these units.

START-UP CHECKLIST

Use the Start-Up Checklist to ensure proper start-up procedures are
followed.

—29—

Advertising