Bryant 582A User Manual

Page 20

Advertising
background image

When the air temperature at the limit switch drops to the
low-temperature setting of the limit switch, the switch closes and
completes the R control circuit. The electric-spark ignition system
cycles and the unit returns to normal heating operation.

H.

AUXILIARY LIMIT SWITCH (ROLLOUT)

The function of the switch is to close the main gas valve in the
event of flame rollout. The switch is located above the main
burners. When the temperature at the auxiliary switch reaches the
maximum allowable temperature, the R control circuit trips,
closing the gas valve and stopping gas flow to the burners. The
indoor (evaporator) fan motor (IFM) and induced draft motor
continue to run until switch is reset. The IGC LED will display
FAULT CODE 7.

III.

START-UP COOLING AND MAKE ADJUSTMENTS

CAUTION:

Complete the required procedures given in

the Pre-Start-Up section before starting the unit.
Do not jumper any safety devices when operating the
unit.
Do not operate the compressor when the outdoor tem-
perature is below 40°F (unless accessory low-ambient kit
is installed).
Do not rapid-cycle the compressor. Allow 5 minutes
between ‘‘on’’ cycles to prevent compressor damage.

A.

CHECKING COOLING CONTROL OPERATION

Start and check the unit for proper cooling control operation as
follows:

1. Place room thermostat SYSTEM switch in OFF position.

Observe that blower motor starts when FAN switch is
placed in ON position and shuts down when FAN switch is
placed in AUTO. position.

2. Place SYSTEM switch in COOL position and FAN switch

in AUTO. position. Set cooling control below room tem-
perature. Observe that compressor, condenser fan, and
evaporator blower motors start. Observe that cooling cycle
shuts down when control setting is satisfied. The evaporator
fan will continue to run for 30 sec.

3. When using an auto-changeover room thermostat, place

both SYSTEM and FAN switches in AUTO. positions.
Observe that unit operates in Heating mode when tempera-
ture control is set to ‘‘call for heating’’ (above room
temperature) and operates in Cooling mode when tempera-
ture control is set to ‘‘call for cooling’’ (below room
temperature).

IMPORTANT: Three-phase, scroll compressor units
(582A048 and 583A030-060) are direction-oriented. These
units must be checked to ensure proper compressor 3-phase
power lead orientation. If not corrected within 5 minutes,
the internal protector shuts off the compressor. The 3-phase
power leads to the unit must be reversed to correct rotation.
When turning backwards, scroll compressors emit elevated
noise levels, and the difference between compressor suction
and discharge pressures may be dramatically lower than
normal.

B.

CHECKING

AND

ADJUSTING

REFRIGERANT

CHARGE

The refrigerant system is fully charged with R-22 refrigerant,
tested, and factory-sealed.

NOTE:

Adjustment of the refrigerant charge is not required

unless the unit is suspected of not having the proper R-22 charge.

A superheat charging chart is attached to the outside of the service
access panel. The chart includes the required suction line tempera-
ture at given suction line pressures and outdoor ambient tempera-
tures.

An accurate superheat, thermocouple- or thermistor-type ther-
mometer, a sling psychrometer, and a gauge manifold are required
when using the superheat charging method for evaluating the unit
charge. Do not use mercury or small dial-type thermometers
because they are not adequate for this type of measurement.

CAUTION:

When evaluating the refrigerant charge, an

indicated adjustment to the specified factory charge must
always be very minimal. If a substantial adjustment is
indicated, an abnormal condition exists somewhere in the
cooling system, such as insufficient airflow across either
coil or both coils.

Proceed as follows:

1. Remove caps from low- and high-pressure service fittings.

2. Using hoses with valve core depressors, attach low- and

high-pressure gauge hoses to low- and high-pressure service
fittings, respectively.

TABLE 7—AIR DELIVERY (CFM) AT INDICATED TEMPERATURE RISE AND RATED HEATING INPUT

HEATING

INPUT

(BTUH)

TEMPERATURE RISE °F

20

25

30

35

40

45

50

55

60

65

70

40,000

1500

1200

1000

857

750

667

600

545

500

60,000

2250

1800

1500

1286

1125

1000

900

818

750

692

90,000

2250

1929

1688

1500

1350

1227

1125

1038

964

115,000

2464

2156

1917

1725

1568

1438

1327

1232

130,000

2786

2438

2167

1950

1773

1625

1500

NOTE: Dashed areas do not fall within the approved temperature rise range of the unit.

TABLE 8—LED INDICATIONS

ERROR CODE

LED INDICATION

Normal Operation

On

Hardware Failure

Off

Fan On/Off Delay Modified

1 Flash

Limit Switch Fault

2 Flashes

Flame Sense Fault

3 Flashes

Four Consecutive Limit Switch Faults

4 Flashes

Ignition Lockout Fault

5 Flashes

Induced-Draft Motor Fault

6 Flashes

Rollout Switch Fault

7 Flashes

Internal Control Fault

8 Flashes

Temporary lock-out (1 hr)

9 Flashes

NOTES:
1. There is a 3-sec. pause between error code displays.
2. If more than one error code exists, all applicable error codes will be
displayed in numerical sequence
3. This chart is on the wiring diagram located inside the burner access panel.

—20—

Advertising