openings. Installation of flexible duct connector is recommended
to prevent transmission of vibration and /or noise to structure. All
ductwork should be secured to the flanges. Insulate and weather-
proof all external ductwork, joints, and roof openings with counter
flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be
ducted through the roof deck to comply with applicable fire codes.

A minimum clearance is not required around ductwork. Cabinet
return-air static shall not exceed -.25 in. wg.

IV.

PROVIDE CLEARANCES

The required minimum operating and service clearances are shown
in Fig. 2 and 3. Adequate combustion, ventilation and condenser
air must be provided in accordance with section 5.3, Air for
Combustion and Ventilation, of the National Fuel Gas Code ANSI
(American National Standards Institute) Z223.1 or applicable

Fig. 4—Roof Curb Dimensions

UNIT SIZE

ODS CATALOG NUMBER

A

IN. (MM)

B

IN. (MM)

C

IN. (MM)

D

IN. (MM)

582A018-042

583A024-036

CPRFCURB006A00

8 (203)

11(279)

161/2 (419)

28-3/4 (730)

CPRFCURB007A00

14 (356)

11(279)

161/2 (419)

28-3/4 (730)

582A048-060

583A042-060

CPRFCURB008A00

8 (203)

16 3/16 (411)

17 3/8 (441)

40-1/4 (1022)

CPRFCURB009A00

14 (356)

16 3/16 (411)

17 3/8 (441)

40-1/4 (1022)

NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Dimensions in ( ) are in millimeters.
4. Roof curb is made of 16-gage steel.
5. Table lists only the dimensions, per part number, that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1-in. thick fiberglass 1 lb density.
8. Dimensions are in inches.
9. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic

conditions. This bracket is available through Micrometl.

C00076

Gasket around

outer edge

Insulated
deck pan

Gasket around

duct

S/A

R/A

HVAC unit

base

*Gasketing

outer flange

Flashing field

supplied

Roofing material

field supplied

Cant strip

field supplied

*Provided with roofcurb

Roof

Duct work

field supplied

Insulation (field

supplied)

Roofcurb*

Wood nailer*

Gasketing

inner flange*

Screw

(NOTE A)

Roof Curb for Small Cabinet

Note A: When unit mounting screw is used,

retainer bracket must also be used.

HVAC unit

base

*Gasketing

outer flange

Flashing field

supplied

Roofing material

field supplied

Cant strip

field supplied

*Provided with roofcurb

Roof

Duct work

field supplied

Insulation (field

supplied)

Roofcurb*

Wood nailer*

Gasketing

inner flange*

Screw

(NOTE A)

Roof Curb for Large Cabinet

Note A: When unit mounting screw is used,

retainer bracket must also be used.

A

B Typ.

Supply opening
(B x C)

Long

Support

D

44

5

/

16

"

(1125.5mm)

Return opening

(B X C)

Insulated
deck pan

Short

Support

C Typ.

—5—