provisions of local building code. In Canada, follow sections 7.2,
7.3, or 7.4 or Can/CGA. (Canadian Gas Association) B149
Installation Codes or applicable provisions of local building code.

Fig. 5—582A and 583A Unit Corner Weights

CORNER #

582A

583A

018

024

030

036

042

048

060

024

030

036

042

048

060

1

47.3

53.2

53.2

59.7

67.5

78.9

85.5

55.1

59.5

61.0

72.6

80.0

88.9

2

44.8

50.4

50.4

56.5

63.9

74.7

81.0

52.2

56.3

57.8

68.8

75.8

84.2

3

77.2

86.8

86.8

97.3

110.1

128.7

139.5

89.9

97.0

99.5

118.4

130.5

145.1

4

79.7

89.6

89.6

106.5

113.6

132.8

144.0

92.8

100.2

102.7

122.2

134.7

149.8

TOTAL WEIGHT

249

280

280

320

355

415

450

290

313

321

382

421

468

C00070

1

2

4

3

x

y

Fig. 6—Slab Mounting Details

C99014

OPTIONAL

RETURN

AIR

OPENING

OPTIONAL

SUPPLY

AIR

OPENING

EVAP.

COIL

COND.

COIL

2"

(50.8mm)

Fig. 7A—Threading Bolt for Rigging

C99067

HANDHOLD

FEED

HOOK

Fig. 7B—Suggested Rigging

SIZE

MAXIMUM WEIGHT

A

B

lb

kg

in.

mm

in.

mm

UNIT 582A

018

271

123.2

20.0

508.0

14.0

355.6

024

302

137.3

22.5

571.5

13.0

330.2

030

302

137.3

21.5

546.1

13.75

349.3

036

342

155.1

22.5

571.5

14.0

355.6

042

377

171.4

21.5

546.1

13.5

342.9

048

437

198.6

22.0

558.5

17.0

432.0

060

472

214.5

22.0

558.5

17.0

432.0

UNIT 583A

024

312

142

22.0

558.5

14.50

368.3

030

335

152

22.0

558.5

15.30

388.6

036

343

156

22.0

558.5

15.30

388.6

042

404

183

23.0

584.2

16.3

414.0

048

443

201

21.5

546.1

16.3

414.0

060

490

222

23.5

596.9

16.3

414.3

C99015

A

1226.3

(48.28”)

914-1371

(36”-54”)

927.57

(36”-52”)

PLACE RIGGING STRAPS IN
BASEPAN SLOT (BELOW RIGGING HOLDS)
BEFORE RIGGING

SEAL STRIP MUST BE IN
PLACE BEFORE PLACING
UNIT ON ROOF CURB

DUCTS

B

—6—