A.

AIR FILTER

CAUTION:

Never operate the unit without a suitable air

filter in the return-air duct system. Always replace the
filter with the same dimensional size and type as origi-
nally installed (See Tables 1 and 2 for recommended filter
sizes).

Inspect air filter(s) at least once each month and replace
(throwaway-type) or clean (cleanable-type) at least twice during
each heating and cooling season or whenever the filter(s) becomes
clogged with dust and/or lint.

B.

EVAPORATOR BLOWER AND MOTOR

NOTE:

All motors are permanently lubricated. Do not attempt to

lubricate these motors.
For longer life, operating economy, and continuing efficiency,
clean accumulated dirt and grease from the blower wheel and
motor annually.

WARNING:

Before cleaning the blower motor and

wheel, disconnect gas supply. Then turn off and tag
electrical power to the unit. Failure to adhere to this
warning could cause serious injury or death.

CLEANING THE BLOWER MOTOR AND WHEEL

1. Remove and disassemble blower assembly as follows:

a. Remove unit access panel.

b. Disconnect motor lead from blower relay (BM). Discon-

nect yellow lead from terminal L2 of the contactor.

c. On all units, remove blower assembly from unit. Re-

move screws securing blower to blower partition and
slide assembly out. Be careful not to tear insulation in
blower compartment.

d. Ensure proper reassembly by marking blower wheel and

motor in relation to blower housing before disassembly.

C00045

Fig. 22—Cooling Charging Chart, 582A042 Units

Fig. 24—Cooling Charging Chart, 582A060 Units

C00048

SUCTION LINE PRESSURE (KILOP

ASCALS)

SUCTION LINE PRESSURE (PSIG)

-1

4

10

16

21

27

32

SUCTION LINE TEMPERATURE (

°

F)

SUCTION LINE TEMPERATURE (

°

C)

689

620

551

483

414

345

276

207

100

90

80

70

60

50

40

30

30

40

50

60

70

80

90

OUTDOOR TEMP

°

F

°

C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

SUCTION LINE PRESSURE (KILOP

ASCALS)

SUCTION LINE PRESSURE (PSIG)

-1

4

10

16

21

27

32

SUCTION LINE TEMPERATURE (

°

F)

SUCTION LINE TEMPERATURE (

°

C)

758

689

620

551

483

414

345

276

110

100

90

80

70

60

50

40

30

40

50

60

70

80

90

OUTDOOR TEMP

°

F

°

C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

C00047

Fig. 23—Cooling Charging Chart, 582A048 Units

SUCTION LINE PRESSURE (KILOP

ASCALS)

SUCTION LINE PRESSURE (PSIG)

-1

4

10

16

21

27

32

SUCTION LINE TEMPERATURE (

°

F)

SUCTION LINE TEMPERATURE (

°

C)

689

620

551

483

414

345

276

207

100

90

80

70

60

50

40

30

30

40

50

60

70

80

90

OUTDOOR TEMP

°

F

°

C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

(024) 60HZ CHARGING CHART

C00049

Fig. 25—Cooling Charging Chart, 583A024 Units