COMBUSTION-AIR BLOWER

Clean periodically to assure proper airflow and heating efficiency.
Inspect blower wheel every fall and periodically during the heating
season. For the first heating season, inspect blower wheel bi-
monthly to determine proper cleaning frequency.

To inspect blower wheel, remove draft hood assembly. Shine a
flashlight into opening to inspect wheel. If cleaning is required,
remove motor and wheel as follows:

1. Remove unit access panel (See Fig. 32).

2. Remove the 7 screws that attach induced-draft motor

mounting plate to blower housing (See Fig. 33).

3. Slide the motor and blower wheel assembly out of the

blower housing (See Fig. 33). Clean the blower wheel. If
additional cleaning is required, continue with Steps 4 and 5.

4. To remove blower, remove 2 setscrews.

5. To remove motor and cooling fan assembly, remove 4

screws that hold blower housing to mounting plate.

6. To reinstall, reverse the procedure outlined above.

E.

LIMIT SWITCH

Remove unit access panel. Limit switch is located on the blower
partition.

F.

BURNER IGNITION

Unit is equipped with a direct spark ignition 100 percent lockout
system. Ignition module is located in the control box. Module
contains a self-diagnostic LED. During servicing, refer to label
diagram for LED interpretation.

If lockout occurs, unit may be reset by either momentarily
interrupting power supply to unit or by turning selector switch to
OFF position at the thermostat.

G.

MAIN BURNERS

At the beginning of each heating season, inspect for deterioration
or blockage due to corrosion or other causes. Observe the main
burner flames and adjust, if necessary.

TABLE 14—582A WET COIL PRESSURE DROP

UNIT SIZE

582A

AIRFLOW

(CFM)

PRESSURE DROP

(IN. WG)

018

500

0.049

600

0.070

700

0.095

024

700

0.077

800

0.100

900

0.127

030

900

0.065

1000

0.080

1100

0.097

036

1100

0.084

1200

0.100

1300

0.177

042

1300

0.103

1400

0.120

1500

0.138

048

1500

0.088

1600

0.100

1700

0.113

060

1900

0.108

2000

0.120

2100

0.132

TABLE 15—583A WET COIL PRESSURE DROP

UNIT SIZE

583A

AIRFLOW

(CFM)

PRESSURE DROP

(IN. WG)

024

700

0.0535

800

0.067

900

0.123

030

900

0.0687

1000

0.083

1100

0.150

036

1100

0.084

1200

0.100

1300

0.177

042

1300

0.099

1400

0.177

1500

0.204

048

1500

0.199

1600

0.137

1700

0.156

060

1900

0.108

2000

0.120

2100

0.132

Fig. 30—Cooling Charging Chart, 583A060 Units

C00054

SUCTION LINE PRESSURE (KILOP

ASCALS)

SUCTION LINE PRESSURE (PSIG)

-1

4

10

16

21

27

32

SUCTION LINE TEMPERATURE (

°

F)

SUCTION LINE TEMPERATURE (

°

C)

689

620

551

483

414

345

276

207

100

90

80

70

60

50

40

30

30

40

50

60

70

80

90

OUTDOOR TEMP

°

F

°

C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

(060) 60HZ CHARGING CHART

Fig. 31—Blower Housing and Flue Collector Box

C99022

INDUCED DRAFT MOTOR MOUNT

VENT HOOD
IN SHIPPING
LOCATION

FLUE
COLLECTOR
BOX

BLOWER
HOUSING

BURNER
RACK

MOUNTING
SCREW

ROLLOUT
SWITCH

—27—

Advertising