e. Loosen setscrew(s) that secures wheel to motor shaft.

Remove screws that secure motor mount brackets to
housing, and slide motor and motor mount out of
housing.

2. Remove and clean blower wheel as follows:

a. Ensure proper reassembly by marking wheel orientation.

b. Lift wheel from housing. When handling and/or cleaning

blower wheel, be sure not to disturb balance weights
(clips) on blower wheel vanes.

c. Remove caked-on dirt from wheel and housing with a

brush. Remove lint and/or dirt accumulations from wheel
and housing with vacuum cleaner, using soft brush
attachment. Remove grease and oil with mild solvent.

d. Reassemble wheel into housing.

e. Reassemble motor into housing. Be sure setscrews are

tightened on motor shaft flats and not on round part of
shaft.

f. Reinstall unit access panel.

3. Restore electrical power to unit. Start unit and check for

proper blower rotation and motor speeds during heating and
cooling cycles.

C.

FLUE GAS PASSAGEWAYS

To inspect the flue collector box and upper areas of the heat
exchanger:

1. Remove the combustion blower wheel and motor assembly

according to directions in the Combustion-Air Blower
section.

2. Remove the 3 screws holding the blower housing to the flue

collector box cover (See Fig. 31–34).

3. Remove the 12 screws holding the flue collector box cover

(See Fig. 33–34) to the heat exchanger assembly. Inspect
the heat exchangers.

4. Clean all surfaces, as required, using a wire brush.

SUCTION LINE PRESSURE (KILOP

ASCALS)

SUCTION LINE PRESSURE (PSIG)

-1

4

10

16

21

27

32

SUCTION LINE TEMPERATURE (

°

F)

SUCTION LINE TEMPERATURE (

°

C)

689

620

551

483

414

345

276

207

100

90

80

70

60

50

40

30

30

40

50

60

70

80

90

OUTDOOR TEMP

°

F

°

C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

(030) 60HZ CHARGING CHART

C99046

Fig. 26—Cooling Charging Chart, 583A030 Units

Fig. 28—Cooling Charging Chart, 583A042 Units

C00052

SUCTION LINE PRESSURE (KILOP

ASCALS)

SUCTION LINE PRESSURE (PSIG)

-1

4

10

16

21

27

32

SUCTION LINE TEMPERATURE (

°

F)

SUCTION LINE TEMPERATURE (

°

C)

689

620

551

483

414

345

276

207

100

90

80

70

60

50

40

30

30

40

50

60

70

80

90

OUTDOOR TEMP

°

F

°

C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

(042) 60HZ CHARGING CHART

SUCTION LINE PRESSURE (KILOP

ASCALS)

SUCTION LINE PRESSURE (PSIG)

-1

4

10

16

21

27

32

SUCTION LINE TEMPERATURE (

°

F)

SUCTION LINE TEMPERATURE (

°

C)

689

620

551

483

414

345

276

207

100

90

80

70

60

50

40

30

30

40

50

60

70

80

90

OUTDOOR TEMP

°

F

°

C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

(036) 60HZ CHARGING CHART

C00051

Fig. 27—Cooling Charging Chart, 583A036 Units

SUCTION LINE PRESSURE (KILOP

ASCALS)

SUCTION LINE PRESSURE (PSIG)

-1

4

10

16

21

27

32

SUCTION LINE TEMPERATURE (

°

F)

SUCTION LINE TEMPERATURE (

°

C)

689

620

551

483

414

345

276

207

100

90

80

70

60

50

40

30

30

40

50

60

70

80

90

OUTDOOR TEMP

°

F

°

C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

(048) 60HZ CHARGING CHART

C00053

Fig. 29—Cooling Charging Chart, 583A048 Units

—26—