Bryant 581A/B User Manual

Page 100

Advertising
background image

100

PERFORMANCE DATA (cont)

COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.

2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil.

3. The SHC is based on 80 F edb temperature of air entering evapo-

rator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B102 (8

1

/

2

TONS) — SUBCOOLING MODE

Temp (F)

Air Ent

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

2550/0.08

3000/0.09

3400/0.11

4250/0.13

Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

114.1

104.1

97.8

116.3

108.5

103.4

117.6

111.9

108.0

122.2

118.9

111.4

SHC

49.8

64.2

81.2

52.6

70.8

89.0

55.4

76.9

95.4

62.0

87.0

107.2

kW

5.57

5.46

5.44

5.59

5.50

5.44

5.60

5.51

5.44

5.62

5.62

5.69

85

TC

107.3

98.4

92.6

111.0

101.8

98.0

113.0

104.2

102.0

117.1

111.4

106.1

SHC

42.2

58.3

76.0

47.1

64.5

83.5

51.2

70.2

89.2

57.3

81.2

101.2

kW

6.32

6.30

6.15

6.32

6.27

6.18

6.34

6.22

6.20

6.30

6.31

6.45

95

TC

101.9

92.4

86.8

105.3

95.5

92.8

107.4

97.7

96.5

112.1

103.7

100.3

SHC

35.4

51.9

70.3

40.1

58.5

77.9

44.9

64.9

83.7

52.1

74.0

94.8

kW

7.06

7.13

6.93

7.06

7.06

6.95

7.06

6.99

6.98

7.01

7.04

7.17

105

TC

94.5

85.4

77.0

97.6

88.3

82.4

99.9

90.6

88.0

104.1

96.1

94.0

SHC

29.7

45.7

63.2

33.9

52.2

70.1

38.0

58.3

75.7

44.4

67.6

88.5

kW

7.99

8.00

7.81

8.01

7.97

7.85

8.02

7.94

7.89

7.96

7.96

8.08

115

TC

86.4

75.0

68.3

89.3

80.2

74.1

91.4

83.2

78.4

96.5

88.4

87.1

SHC

24.0

38.7

56.4

27.4

45.6

62.9

31.1

51.9

67.0

37.0

60.8

81.8

kW

8.91

8.83

8.66

8.93

8.86

8.76

8.97

8.86

8.84

8.91

8.93

8.90

125

TC

78.6

65.5

60.2

81.3

68.9

64.7

83.3

71.6

68.2

88.5

78.8

78.9

SHC

18.3

32.0

48.8

21.2

38.0

53.5

24.1

44.1

57.5

29.4

53.3

73.8

kW

9.81

9.65

9.53

9.86

9.68

9.64

9.89

9.71

9.75

9.90

9.72

9.88

581B102 (8

1

/

2

TONS) — HOT GAS REHEAT MODE

Temp (F)

Air Ent

Condenser

(Edb)

Air Entering Evaporator — Ewb (F)

75 Dry Bulb

62.5 Wet Bulb

(50% Relative)

75 Dry Bulb

64 Wet Bulb

(55% Relative)

75 Dry Bulb

65.3 Wet Bulb

(60% Relative)

Air Entering Evaporator — Cfm

2550

3000

3400

4250

2550

3000

3400

4250

2550

3000

3400

4250

80

TC

43.44

46.26

48.45

52.38

45.26

48.15

50.39

54.43

46.84

49.79

52.08

56.20

SHC

12.34

16.78

20.29

26.74

5.79

10.15

13.60

19.93

0.11

4.40

7.80

14.03

kW

6.31

6.31

6.31

6.31

6.05

6.05

6.05

6.05

5.83

5.83

5.83

5.83

75

TC

44.33

47.00

49.06

52.78

46.12

48.85

50.97

54.78

47.67

50.46

52.63

56.52

SHC

12.92

17.12

20.44

26.54

6.81

10.94

14.20

20.20

1.51

5.58

8.79

14.70

kW

6.38

6.38

6.8

6.38

6.15

6.15

6.15

6.15

5.95

5.95

5.95

5.95

70

TC

45.22

47.73

49.68

53.18

46.98

49.55

51.55

55.14

48.51

51.14

53.18

56.84

SHC

13.50

17.47

20.59

26.34

7.83

11.73

14.81

20.46

2.92

6.76

9.79

15.36

kW

6.46

6.46

6.46

6.46

6.25

6.25

6.25

6.25

6.07

6.07

6.07

6.07

60

TC

46.99

49.19

50.90

53.97

48.70

50.96

52.71

55.86

50.18

52.49

54.27

57.49

SHC

14.67

18.15

20.90

25.95

9.88

13.31

16.01

20.99

5.73

9.11

11.78

16.68

kW

6.60

6.60

6.60

6.60

6.45

6.45

6.45

6.45

6.32

6.32

6.32

6.32

50

TC

48.77

50.66

52.13

54.77

50.42

52.36

53.87

56.57

51.85

53.83

55.37

58.14

SHC

15.83

18.83

21.20

25.56

11.93

14.89

17.22

21.51

8.55

11.47

13.77

18.01

kW

6.74

6.74

6.74

6.74

6.64

6.64

6.64

6.64

6.56

6.56

6.56

6.56

40

TC

50.54

52.13

53.35

55.56

52.14

53.76

55.02

57.29

53.53

55.18

56.47

58.78

SHC

17.00

19.52

21.51

25.16

13.98

16.47

18.43

22.04

11.36

13.82

15.76

19.33

kW

6.88

6.88

6.88

6.88

6.84

6.84

6.84

6.84

6.81

6.81

6.81

6.81

BF

Bypass Factor

Edb

Entering Dry Bulb

Ewb — Entering Wet Bulb
kW

Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air

leaving evaporator coil (h

lwb

)

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

581

B0

36

-15

0

Advertising