211

PERFORMANCE DATA (cont)

COOLING CAPACITIES — STANDARD UNITS (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-

rator coil (hlwb)

Where: hewb = Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

4. Use chart below for bypass factor.

581A240 (20 Tons)

Temp (F)

Air Ent

Cond

Evap Air — Cfm/BF

6,000/0.04

7,000/0.05

8,000/0.05

Evap Air — Ewb (F)

54

58

62

67

72

76

80

54

58

62

67

72

76

80

54

58

62

67

72

76

80

60

TC

235

242

248

267

288

306

323

247

251

256

274

296

312

330

257

259

262

279

300

317

333

SHC

235

224

212

178

143

115

86.6

247

238

230

191

151

119

87

257

251

246

204

159

123

86.7

kW

11.5

11.6

11.7

12

12.4

12.7

13

11.7

11.8

11.8

12.1

12.5

12.8

13.1

11.9

11.9

11.9

12.2

12.6

12.9

13.1

70

TC

231

237

242

261

282

300

316

242

246

250

268

289

305

323

252

254

256

273

293

310

326

SHC

231

220

209

175

141

113

84.5

242

234

227

189

149

117

84.9

252

247

243

201

156

120

84.6

kW

13.1

13.2

13.3

13.6

14

14.3

14.6

13.3

13.3

13.4

13.7

14.1

14.4

14.8

13.4

13.5

13.5

13.8

14.2

14.5

14.8

75

TC

228

234

239

257

278

295

311

239

243

246

264

285

301

318

249

250

252

269

290

305

322

SHC

228

218

208

174

139

112

83.1

239

232

225

187

147

115

83.6

249

245

241

199

155

119

83.5

kW

13.9

14

14.1

14.5

14.9

15.2

15.6

14.1

14.2

14.2

14.6

15

15.3

15.7

14.3

14.3

14.4

14.7

15.1

15.4

15.8

85

TC

223

227

231

250

270

287

303

234

236

238

256

277

292

310

243

244

245

261

282

296

314

SHC

223

213

204

171

136

109

80.5

234

227

221

184

144

112

80.9

243

240

236

196

152

116

81.3

kW

15.6

15.7

15.8

16.2

16.6

17.1

17.4

15.8

15.9

15.9

16.3

16.8

17.2

17.6

16

16.1

16.1

16.5

16.9

17.3

17.7

95

TC

216

219

223

241

260

277

292

226

228

230

247

267

282

298

235

235

236

251

272

285

303

SHC

216

208

200

167

132

105

77.2

226

221

217

180

141

109

77.7

235

233

231

192

148

112

78

kW

17.4

17.5

17.6

18.1

18.6

19

19.4

17.7

17.7

17.8

18.2

18.7

19.1

19.6

17.9

17.9

17.9

18.3

18.9

19.2

19.7

105

TC

208

211

214

231

249

265

279

218

219

220

236

256

270

285

226

226

226

241

260

273

290

SHC

208

202

195

163

129

101

73.6

218

215

212

176

137

105

74

226

226

225

188

145

108

74.4

kW

19.3

19.4

19.5

20

20.6

21

21.5

19.6

19.6

19.7

20.2

20.8

21.2

21.6

19.9

19.9

19.9

20.3

20.9

21.3

21.8

115

TC

200

202

204

220

237

253

266

209

210

210

225

243

257

271

217

217

217

229

248

260

275

SHC

200

195

190

158

124

97.2

69.5

209

207

206

171

132

101

70

217

217

217

183

140

104

70.4

kW

21.3

21.4

21.5

22

22.7

23.2

23.6

21.7

21.7

21.7

22.2

22.9

23.3

23.8

21.9

21.9

21.9

22.4

23

23.4

23.9

125

TC

191

192

193

208

224

239

251

199

199

200

212

230

243

255

207

207

206

216

232

245

257

SHC

191

188

185

153

120

92.8

65.3

199

199

199

166

128

96.4

65.7

207

207

206

178

135

99.8

65.5

kW

23.5

23.5

23.6

24.2

24.8

25.4

25.9

23.8

23.8

23.8

24.4

25

25.5

26

24.1

24.1

24.1

24.5

25.1

25.7

26.1

581A240 (20 Tons) (cont)

Temp (F)

Air Ent

Cond

Evap Air — Cfm/BF

9,000/0.06

10,000/0.07

Evap Air — Ewb (F)

54

58

62

67

72

76

80

54

58

62

67

72

76

80

60

TC

265

266

267

284

305

321

338

272

272

272

287

307

325

340

SHC

265

262

260

216

166

126

87

272

271

271

227

173

130

86.7

kW

12

12

12

12.3

12.7

12.9

13.2

12.1

12.1

12.1

12.4

12.7

13

13.3

70

TC

260

261

261

277

298

315

331

266

267

267

281

301

317

333

SHC

260

258

256

213

164

124

85

266

267

267

225

171

127

84.7

kW

13.6

13.6

13.6

13.9

14.3

14.6

14.9

13.7

13.7

13.7

14

14.3

14.6

15

75

TC

256

257

258

273

294

310

326

263

263

263

277

296

312

327

SHC

256

255

254

211

162

123

83.7

263

263

263

223

169

126

83.4

kW

14.5

14.5

14.5

14.8

15.2

15.5

15.8

14.6

14.6

14.6

14.9

15.2

15.6

15.9

85

TC

250

250

250

265

285

301

316

257

256

256

268

287

303

317

SHC

250

250

249

208

159

120

81

257

256

256

220

166

123

80.7

kW

16.2

16.2

16.2

16.5

17

17.4

17.7

16.4

16.4

16.4

16.6

17

17.4

17.7

95

TC

242

242

242

255

274

288

304

248

248

248

258

276

292

306

SHC

242

242

242

204

155

116

77.8

248

248

248

215

162

120

77.6

kW

18.1

18.1

18.1

18.4

18.9

19.3

19.7

18.3

18.3

18.2

18.5

19

19.4

19.7

105

TC

233

233

233

244

263

275

291

239

239

239

247

264

279

291

SHC

233

233

233

200

152

112

74.2

239

239

239

211

158

116

73.9

kW

20.1

20.1

20.1

20.4

21

21.4

21.8

20.3

20.2

20.2

20.5

21

21.5

21.8

115

TC

223

223

223

232

250

262

276

229

228

228

235

251

263

276

SHC

223

223

223

195

147

108

70.2

229

228

228

206

154

111

69.9

kW

22.2

22.1

22.1

22.5

23.1

23.5

24

22.3

22.3

22.3

22.6

23.1

23.6

24

125

TC

213

212

212

219

234

247

258

218

217

217

222

235

248

259

SHC

213

212

212

189

142

103

65.4

218

217

217

200

148

106

65.2

kW

24.3

24.3

24.3

24.6

25.2

25.7

26.2

24.5

24.5

24.5

24.7

25.3

25.8

26.2

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

tldb = tedb –

sensible capacity (Btuh)

1.10 x cfm

hlwb = hewb –

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

CFM

ENTERING WET-BULB (F)

54

58

62

67

72

76

80

Bypass Factor

6,000

0.386

0.197

0.108

0.109

0.134

0.000

0.000

7,000

0.444

0.260

0.131

0.121

0.138

0.000

0.000

8,000

0.492

0.321

0.163

0.133

0.145

0.000

0.000

9,000

0.532

0.375

0.205

0.146

0.154

0.000

0.000

10,000

0.566

0.420

0.245

0.158

0.164

0.000

0.000

5

81A1

55-

30
0