TYPICAL WIRING SCHEMATICS — 580F036-151 (cont)

LEGEND

IAQ — Indoor Air Quality
LA

Low Ambient Lockout Device

POT — Potentiometer
OAT — Outdoor-Air Temperature
RAT — Return-Air Temperature

EconoMi$er IV Wiring — 580F036-151 Units

NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.

NOTE:
Potentiometer Defaults Settings:
Power Exhaust

Middle

Minimum Pos.

Fully Closed

DCV Max.

Middle

DCV Set

Middle

Enthalpy

C Setting

ECONOMIZER NOTES:

1. 620 ohm, 1 watt 5% resister should be removed only when using differential

enthalpy or dry bulb.

2. If a separate field supplied 24v transformer is used for the IAQ sensor

power supply, it cannot have the secondary of the transformer grounded.

3. For field installed remote minimum position POT, remove black wire jumper

between P and P1 and set control minimum position POT to the minimum
position.

EconoMi$er2 Wiring — 580F036-151 Units

a48-7910

4

3

5

2

8

6

7

1

10

11

9

12

PINK

VIOLET

BLACK

BLUE

YELLOW

NOTE 1

NOTE 2

RUN

500 OHM
RESISTOR

-

+

OPTIONAL CO

SENSOR 4 - 20 mA

OUTPUT

50HJ540573

ACTUATOR

ASSEMBLY

RED

WHITE

ECONOMISER2 PLUG

DIRECT DRIVE

ACTUATOR

2

a48-8209

58

0F0

3

6

-15

1