579f180-300 – Bryant 581A/B User Manual

Page 12

Advertising
background image

12

ARI* CAPACITY RATINGS — 579F180-300

LOW HEAT UNITS

HIGH HEAT UNITS

LEGEND

*Air Conditioning and Refrigeration Institute.
NOTES:

1. Rated in accordance with ARI Standards 360 and 270.
2. The 579F300 is beyond the scope of the ARI Certification

Program.

3. ARI ratings are net values, reflecting the effects of circulating fan

heat.

4. Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air tempera-
ture and 95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature
and 80 F db outdoor entering-air temperature.

HEATING CAPACITIES AND EFFICIENCIES — 579F180-300

*All units are 2-stage heat.
NOTE: Minimum allowable temperature of mixed-air entering the heat exchanger during first-stage
heating is 45 F. There is no minimum mixed-air temperature limitation during second-stage heating.
For entering-air temperatures below 45 F both stages of heat must be energized together to minimize
condensation issues and ensure proper unit operation.

AIR QUANTITY LIMITS

LOW OUTDOOR TEMPERATURE

OPERATING LIMITS (F)

UNIT
579F

NOMINAL

TONS

NET COOLING

CAPACITY

(Btuh)

TOTAL

WATTS

EER

SOUND

RATING

(dB)

IPLV

180

15

174,000

20,128

8.6

88

9.3

216

18

188,000

21,619

8.7

88

9.5

240

20

220,000

25,513

8.6

94

8.7

300

25

268,000

31,068

8.6

94

9.2

UNIT
579F

NOMINAL

TONS

NET COOLING

CAPACITY

(Btuh)

TOTAL

WATTS

EER

SOUND

RATING

(dB)

IPLV

180

15

174,000

20,154

8.6

88

9.3

216

18

186,000

21,798

8.5

88

9.3

240

20

218,000

25,719

8.5

94

8.5

300

25

268,000

31,600

8.5

94

8.9

dB

Sound Levels (decibels)

db

Dry Bulb

EER — Energy Efficiency Ratio
IPLV — Integrated Part-Load Values
wb

Wet Bulb

UNIT
579F

HEATING INPUT

(Btuh)

Stage 2/Stage 1*

OUTPUT CAPACITY

(Btuh)

TEMPERATURE

RISE (F)

STEADY-STATE

EFFICIENCY (%)

MINIMUM

HEATING CFM

180230

230,000/172,000

186,000

15-45

81.0

3830

180300

300,000/225,000

243,000

30-60

81.0

3750

216275

275,000/206,000

223,000

15-45

81.0

4580

216360

360,000/270,000

292,000

20-50

81.0

5400

240275

275,000/206,000

223,000

15-45

81.0

4580

240360

360,000/270,000

292,000

20-50

81.0

5400

300275

275,000/206,000

223,000

15-45

81.0

4580

300360

360,000/270,000

292,000

20-50

81.0

5400

UNIT 579F

MINIMUM CFM

MAXIMUM CFM

180

4500

7,500

216

5400

9,000

240

6000

10,000

300

7000

11,250

UNITS

TEMPERATURE

All

40

180 and 216 with Low Ambient Kit

10

240 and 300 with Low Ambient Kit

25

All with Motormaster® Head Pressure Control

–20

Advertising