ELECTRICAL DATA

LEGEND

*Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combina-

tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage
is greater than 2%.
Use the following formula to determine the per-
cent voltage imbalance.
% Voltage Imbalance

EXAMPLE: Supply voltage is 460-3-60.

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent voltage imbalance.

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.

UNIT
579F

NOMINAL

VOLTAGE

(3 Ph, 60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

COMBUSTION

FAN MOTOR

POWER

SUPPLY

No. 1

No. 2

Min Max RLA LRA RLA LRA Qty Hp FLA

(ea)

Hp

FLA

FLA LRA

FLA

MCA

MOCP*

180

(15 Tons)

208/230

187

253

28.8 195

28.8

195

3

0.5

1.7

3.7

10.5/11.0

0.57

81/81

100/100

4.6

18.8

0.57

85/86

110/110

460

414

508

14.7

95

14.7

95

3

0.5

0.8

3.7

4.8

0.30

40

50

2.3

6.0

0.30

43

50

575

518

633

10.8

80

10.8

80

3

0.5

0.8

3.0

3.9

0.57

30

40

2.1

4.8

0.57

32

40

216

(18 Tons)

208/230

187

253

30.1 225

28.8

195

3

0.5

1.7

5.0

15.8/15.8

0.57

87/87

110/110

4.6

18.8

0.57

92/92

110/110

460

414

508

15.5 114

14.7

95

3

0.5

0.8

5.0

7.9

0.30

44

50

2.3

6.0

0.30

47

60

575

518

633

12.1

80

10.8

80

3

0.5

0.8

5.0

6.0

0.57

34

40

2.1

4.8

0.57

36

40

240

(20 Tons)

208/230

187

253

37.8 239

30.1

225

2

1

6.6

7.5

25.0/25.0

0.57

116/116 150/150

4.6

18.8

0.57

120/120 150/150

460

414

508

17.2 125

15.5

114

2

1

3.3

7.5

13.0

0.30

57

70

2.3

6.0

0.30

59

70

575

518

633

12.4

80

12.1

80

2

1

3.4

7.5

10.0

0.57

44

50

2.1

4.8

0.57

46

50

300

(25 Tons)

208/230

187

253

41.0 350

37.8

239

2

1

6.6

10.0 28.0/28.0

0.57

130/130 150/150

4.6

18.8

0.57

135/135 175/175

460

414

508

21.8 158

17.2

125

2

1

3.3

10.0

14.6

0.30

66

80

2.3

6.0

0.30

68

80

575

518

633

17.3 125

12.4

80

2

1

3.4

10.0

13.0

0.57

54

70

2.1

4.8

0.57

56

70

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

AB = 452 v
BC = 464 v
AC = 455 v

Average Voltage = 452 + 464 + 455

3

=

1371

3

= 457

% Voltage Imbalance = 100 x

7

457

= 1.53%