Fan performance using accessory power exhaust, Altitude compensation, 240 performance data (cont) – Bryant 581A/B User Manual

Page 240

Advertising
background image

240

PERFORMANCE DATA (cont)

ALTITUDE COMPENSATION* — 581A155,180

(Natural Gas Units)

*Includes a 4% input reduction per each 1,000 feet.

†Orifices available through your Bryant dealer.

ALTITUDE COMPENSATION — 581A155,180

(LP Gas Units)

ALTITUDE COMPENSATION — 581A210-300

(Natural Gas)

ALTITUDE COMPENSATION — 581A210-300

(LP Gas)

ALTITUDE DERATING FACTOR*

*Derating of the unit is not required unless the heating value of the gas

exceeds the values listed in the table above, or if the elevation exceeds
6000 ft. Derating conditions must be 4% per thousand ft above 2000 ft.
For example, at 4000 ft, if the heating value of the gas exceeds
1000 Btu/ft

3

, the unit will require a 16% derating. For elevations above

6000 ft, the same formula applies. For example, at 7000 ft, the unit will
require a 28% derating of the maximum heating value per the National
Fuel Gas Code.

IMPORTANT: Local utility companies may be reducing heat content of
gas at altitudes above 2000 ft. If this is being done, changing spuds may
not be required.

EVAPORATOR-FAN MOTOR EFFICIENCY —

581A155,180

NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency
requirements as established by the Energy Policy Act of 1992 (EPACT)
effective October 24, 1997.

ELEVATION

(ft)

NATURAL GAS ORIFICE SIZE†

Low Heat

High Heat

0-3,000

30

29

3,000- 7,000

31

30

7,000- 9,000

32

31

9,000-10,000

33

31

above 10,000

35

32

ELEVATION

(ft)

LIQUID PROPANE ORIFICE SIZE

Low Heat and High Heat

0-2,000

36

2,000

37

3,000

38

4,000

38

5,000

39

6,000

40

7,000

41

8,000

41

9,000

42

10,000

43

ELEVATION

(ft)

ORIFICE SIZE — NATURAL GAS

Low

Heat

Medium

Heat

High Heat

(6 Cell)

High Heat

(8 Cell)

0-2,000

29

30

29

29

2,000

29

30

29

29

3,000

30

31

30

30

4,000

30

31

30

30

5,000

30

31

30

30

6,000

30

31

30

30

7,000

31

32

31

31

8,000

31

32

31

31

9,000

31

32

31

31

above 10,000

32

33

32

32

Fan Performance Using Accessory

Power Exhaust (581A155,180)

a50-4028

ELEVATION

(ft)

ORIFICE SIZE — LP GAS

Low

Heat

Medium

Heat

High Heat

(6 Cell)

High Heat

(8 Cell)

0-2,000

35

38

35

35

2,000

36

39

36

36

3,000

36

39

36

36

4,000

37

40

37

37

5,000

37

40

37

37

6,000

38

41

38

38

7,000

39

42

39

39

8,000

40

43

40

40

9,000

41

44

41

41

above 10,000

42

45

42

42

ELEVATION

(ft)

MAXIMUM HEATING VALUE

(Btu/ft

3

)

0-2,000

1,100

2,001-3,000

1,050

3,001-4,000

1,000

4,001-5,000

950

5,001-6,000

900

MOTOR

HORSEPOWER

MOTOR EFFICIENCY

(%)

3.0

81.7

2.9, 3.7

85.8

5.0

87.5

581

A155

-3

00

Advertising