212 performance data (cont), Cooling capacities — standard units (cont) – Bryant 581A/B User Manual

Page 212

Advertising
background image

212

PERFORMANCE DATA (cont)

COOLING CAPACITIES — STANDARD UNITS (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-

rator coil (hlwb)

Where: hewb = Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

4. Use chart below for bypass factor.

581A300 (25 Tons)

Temp (F)

Air Ent

Cond

Evap Air — Cfm/BF

7,500/0.05

8,250/0.06

9,500/0.07

Evap Air — Ewb (F)

54

58

62

67

72

76

80

54

58

62

67

72

76

80

54

58

62

67

72

76

80

60

TC

287

296

304

331

359

385

408

297

304

310

336

367

390

414

311

315

319

345

375

398

421

SHC

287

274

261

220

178

145

110

297

285

273

229

185

148

110

311

303

294

246

194

152

111

kW

15.5

15.7

15.9

16.5

17.3

17.9

18.6

15.7

15.9

16

16.7

17.4

18.1

18.7

16

16.1

16.2

16.9

17.6

18.3

19

70

TC

279

286

293

318

345

367

392

288

293

298

323

350

372

397

301

303

306

329

357

381

403

SHC

279

267

255

214

173

139

105

288

278

268

224

178

142

105

301

294

287

239

188

147

105

kW

17

17.2

17.3

18

18.7

19.3

20

17.2

17.3

17.5

18.1

18.8

19.4

20.1

17.5

17.6

17.7

18.3

19

19.7

20.3

75

TC

275

281

287

311

338

360

383

283

288

293

316

343

365

388

296

298

300

323

349

372

394

SHC

275

264

252

212

170

136

102

283

274

265

221

176

139

103

296

290

284

237

185

144

103

kW

17.9

18.1

18.2

18.8

19.5

20.1

20.8

18.1

18.2

18.4

18.9

19.7

20.3

20.9

18.4

18.5

18.5

19.1

19.8

20.5

21.1

85

TC

267

272

277

299

324

345

366

274

278

282

304

329

350

370

286

287

289

311

334

355

375

SHC

267

257

247

207

165

131

97.3

274

267

259

216

171

134

97.3

286

282

278

232

180

139

97.3

kW

19.8

19.9

20

20.6

21.2

21.8

22.4

20

20.1

20.1

20.7

21.4

22

22.6

20.2

20.3

20.3

20.9

21.5

22.1

22.7

95

TC

259

263

267

288

311

331

350

267

270

273

293

315

335

354

278

279

281

299

322

340

358

SHC

259

251

242

202

160

126

92.5

267

261

255

212

166

129

92.5

278

276

273

227

175

134

92.4

kW

22.1

22.2

22.3

22.8

23.4

23.9

24.5

22.3

22.4

22.5

22.9

23.5

24

24.6

22.6

22.6

22.6

23.1

23.6

24.2

24.7

105

TC

253

256

260

279

301

318

335

260

262

264

282

304

322

338

269

270

270

287

308

326

342

SHC

253

246

239

198

156

122

87.9

260

255

250

207

162

125

87.8

269

268

267

222

171

129

87.7

kW

24.9

25

25.1

25.4

25.9

26.4

26.9

25.1

25.1

25.1

25.5

26

26.5

26.9

25.2

25.2

25.2

25.6

26.1

26.6

27.1

115

TC

246

249

252

270

291

305

320

253

255

256

274

294

309

323

262

262

262

277

298

312

328

SHC

246

240

235

195

152

118

83.5

253

250

246

204

158

121

83.4

262

261

261

218

167

125

83.9

kW

28.1

28.2

28.3

28.6

29

29.3

29.6

28.3

28.3

28.3

28.6

29

29.4

29.7

28.4

28.4

28.4

28.7

29.1

29.4

29.9

125

TC

238

240

242

259

279

293

305

245

246

246

262

281

295

310

253

253

253

266

284

298

313

SHC

238

234

230

190

148

114

79.2

245

243

240

199

153

116

79.7

253

253

253

214

162

120

79.9

kW

31.6

31.7

31.7

32

32.4

32.6

32.9

31.8

31.8

31.8

32.1

32.4

32.7

33

31.9

31.9

31.9

32.1

32.5

32.7

33.1

581A300 (25 Tons) (cont)

Temp (F)

Air Ent

Cond

Evap Air — Cfm/BF

10,750/0.08

12,000/0.09

Evap Air — Ewb (F)

54

58

62

67

72

76

80

54

58

62

67

72

76

80

60

TC

322

324

327

351

380

404

429

332

333

334

357

386

410

432

SHC

322

317

313

260

203

157

111

332

330

329

276

212

162

111

kW

16.3

16.4

16.4

17

17.8

18.5

19.2

16.6

16.6

16.6

17.2

18

18.6

19.2

70

TC

311

312

314

336

364

386

408

320

320

321

341

368

392

414

SHC

311

308

305

255

198

151

105

320

320

319

269

206

156

106

kW

17.8

17.8

17.9

18.4

19.2

19.8

20.5

18

18

18

18.5

19.3

20

20.6

75

TC

306

307

308

329

356

378

398

315

315

315

333

360

383

404

SHC

306

304

302

252

195

149

103

315

314

314

266

203

153

103

kW

18.7

18.7

18.7

19.3

20

20.6

21.3

18.9

18.9

18.9

19.4

20.1

20.8

21.4

85

TC

295

296

297

315

340

362

379

303

303

303

319

344

365

385

SHC

295

295

294

246

189

144

97.3

303

303

303

260

198

148

97.9

kW

20.5

20.5

20.5

21

21.7

22.3

22.8

20.7

20.7

20.7

21.1

21.8

22.4

23

95

TC

286

286

286

303

327

344

364

293

293

294

307

330

347

366

SHC

286

286

286

241

185

138

93

293

293

294

255

193

142

92.8

kW

22.7

22.7

22.7

23.1

23.8

24.3

24.9

22.9

22.9

22.9

23.2

23.9

24.4

24.9

105

TC

277

277

277

290

312

329

347

284

284

285

295

314

331

352

SHC

277

277

277

236

179

133

88.3

284

284

285

250

188

137

88.7

kW

25.4

25.4

25.4

25.7

26.2

26.7

27.2

25.5

25.6

25.6

25.8

26.3

26.7

27.3

115

TC

268

269

269

281

300

315

332

274

274

275

283

303

317

333

SHC

268

269

269

232

176

129

84.4

274

274

275

245

184

133

84

kW

28.5

28.5

28.5

28.7

29.2

29.5

30

28.6

28.6

28.6

28.8

29.2

29.5

30

125

TC

260

259

259

269

287

300

316

265

265

264

271

289

302

318

SHC

260

259

259

227

171

125

80

265

265

264

240

179

129

80.1

kW

32

32

32

32.1

32.5

32.8

33.2

32.1

32.1

32.1

32.2

32.5

32.8

33.3

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

tldb = tedb –

sensible capacity (Btuh)

1.10 x cfm

hlwb = hewb –

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

CFM

ENTERING WET-BULB (F)

54

58

62

67

72

76

80

Bypass Factor

7,500

0.407

0.208

0.097

0.104

0.123

0.000

0.000

8,250

0.443

0.256

0.110

0.112

0.128

0.000

0.000

9,500

0.494

0.324

0.138

0.123

0.136

0.000

0.000

10,750

0.536

0.380

0.181

0.134

0.145

0.000

0.000

12,000

0.571

0.427

0.232

0.145

0.154

0.000

0.000

581

A155

-3

00

Advertising