35 performance data (cont), Cooling capacities (cont) – Bryant 581A/B User Manual

Page 35

Advertising
background image

35

PERFORMANCE DATA (cont)

COOLING CAPACITIES (cont)

Standard Ratings

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil.

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

580F120 (10 TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

3000/0.095

4000/0.125

5000/0.15

Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

135.8

124.8

112.0

142.4

130.6

119.8

146.5

134.2

123.7

SHC

66.8

82.6

97.4

73.2

93.4

112.7

79.7

104.4

123.1

kW

9.76

9.41

9.10

10.00

9.61

9.27

10.17

9.75

9.41

85

TC

130.0

119.6

104.0

136.0

125.0

114.5

140.0

127.9

118.8

SHC

64.3

80.5

93.8

71.1

91.7

110.2

77.5

101.8

118.7

kW

10.41

10.07

9.74

10.67

10.28

9.94

10.84

10.41

10.09

95

TC

124.1

113.7

96.7

129.5

118.9

106.9

132.8

122.0

114.1

SHC

62.2

78.4

90.0

69.1

89.8

105.9

74.9

100.1

114.0

kW

11.13

10.78

10.40

11.38

10.99

10.63

11.52

11.14

10.83

105

TC

118.1

104.6

87.9

122.7

111.8

98.5

126.0

115.1

108.0

SHC

60.4

74.9

85.2

66.9

87.7

98.5

73.1

98.3

108.0

kW

11.93

11.52

11.10

12.13

11.74

11.41

12.27

11.89

11.65

115

TC

115.0

98.0

84.2

120.0

103.8

93.4

122.6

109.8

102.8

SHC

59.4

72.4

83.4

66.4

84.8

93.4

72.8

96.9

102.8

kW

12.26

11.82

11.40

12.48

12.06

11.78

12.60

12.20

12.00

580F121 (10 TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

3000/0.095

4000/0.125

5000/0.15

Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

138.2

127.0

114.0

145.0

132.9

122.0

149.1

136.6

125.9

SHC

68.0

84.1

99.1

74.5

95.1

114.7

81.1

106.3

125.3

kW

8.37

8.07

7.80

8.57

8.24

7.95

8.72

8.36

8.07

85

TC

132.3

121.7

105.9

138.4

127.2

116.6

142.5

130.2

120.9

SHC

65.5

81.9

95.5

72.4

93.3

112.2

78.9

103.6

120.8

kW

8.92

8.63

8.35

9.15

8.81

8.52

9.29

8.92

8.65

95

TC

126.3

115.7

98.4

131.8

121.0

108.8

135.2

124.2

116.1

SHC

63.3

79.8

91.6

70.3

91.4

107.8

76.2

101.9

116.0

kW

9.54

9.24

8.91

9.75

9.42

9.11

9.87

9.55

9.28

105

TC

120.2

106.5

89.5

124.9

113.8

100.3

128.3

117.2

109.9

SHC

61.5

76.2

86.7

68.1

89.3

100.3

74.4

100.1

109.9

kW

10.23

9.87

9.51

10.40

10.06

9.78

10.52

10.19

9.99

115

TC

117.1

99.8

85.7

122.2

105.7

95.1

124.8

111.8

104.6

SHC

60.5

73.7

84.9

67.6

86.3

95.1

74.1

98.6

104.6

kW

10.51

10.13

9.77

10.70

10.34

10.10

10.80

10.46

10.29

580F150 (12

1

/

2

TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

3750/0.08

4500/0.09

5000/0.10

6250/0.12

Air Entering Evaporator — Ewb (F)

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

175.6

162.2

149.2

181.0

167.5

154.2

182.9

170.2

156.4

187.2

174.7

161.8

SHC

85.7

107.3

128.0

91.4

116.2

140.3

94.2

122.2

146.5

102.1

135.3

160.7

kW

11.16

10.85

10.57

11.32

11.00

10.69

11.37

11.07

10.73

11.49

11.19

10.87

85

TC

169.3

155.7

140.6

174.2

160.7

147.0

176.9

163.0

149.7

181.5

167.3

155.8

SHC

83.9

104.8

124.0

89.6

113.9

137.0

92.7

119.7

143.6

100.9

133.4

155.6

kW

12.15

11.78

11.42

12.31

11.94

11.58

12.39

12.01

11.63

12.53

12.14

11.82

95

TC

161.9

148.9

132.0

166.8

153.5

139.1

169.5

155.7

142.8

173.2

159.5

149.6

SHC

81.4

102.0

119.8

87.0

111.1

133.2

90.7

117.3

140.2

98.3

130.8

149.6

kW

13.12

12.72

12.28

13.30

12.89

12.46

13.40

12.97

12.56

13.54

13.11

12.78

105

TC

154.9

141.3

123.0

158.8

145.4

130.2

160.9

147.6

135.0

165.3

151.2

143.2

SHC

79.0

99.2

115.5

84.5

108.2

128.1

87.8

114.3

134.9

96.6

127.8

143.1

kW

14.16

13.66

13.17

14.31

13.82

13.35

14.38

13.91

13.48

14.58

14.07

13.77

115

TC

146.2

132.2

113.1

150.5

137.0

122.4

152.3

139.4

127.8

155.2

142.7

136.0

SHC

76.1

95.7

110.3

81.7

105.2

122.3

85.0

111.6

127.7

92.9

125.0

135.8

kW

15.09

14.57

14.07

15.30

14.76

14.25

15.37

14.87

14.43

15.49

15.02

14.73

BF

Bypass Factor

Edb

Entering Dry-Bulb

Ewb —

Entering Wet-Bulb

kW

Compressor Motor Power Input

Ldb

Leaving Dry-Bulb

Lwb —

Leaving Wet-Bulb

SHC —

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h

lwb

)

h

lwb

=

h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

58
0

F

03
6-

15
1

Advertising