210

PERFORMANCE DATA (cont)

COOLING CAPACITIES — STANDARD UNITS (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-

rator coil (hlwb)

Where: hewb = Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

4. Use chart below for bypass factor.

581A210 (18 Tons)

Temp (F)

Air Ent

Cond

Evap Air — Cfm/BF

5400/0.05

6300/0.06

7200/0.07

Evap Air — Ewb (F)

54

58

62

67

72

76

80

54

58

62

67

72

76

80

54

58

62

67

72

76

80

60

TC

202

206

211

229

248

263

279

212

215

218

235

254

269

285

220

221

223

239

259

273

289

SHC

202

193

184

155

124

99.3

74.7

212

205

199

166

131

103

74.9

220

216

213

177

138

106

75

kW

10.2

10.3

10.4

10.6

10.8

11

11.2

10.4

10.4

10.4

10.7

10.9

11.1

11.3

10.5

10.5

10.5

10.7

11

11.2

11.4

70

TC

197

202

206

223

242

256

272

207

209

212

228

247

262

277

215

216

217

233

252

267

282

SHC

197

189

181

152

122

97

72.5

207

202

196

163

129

101

72.7

215

212

210

174

135

104

72.8

kW

11.4

11.5

11.5

11.8

12

12.2

12.5

11.6

11.6

11.6

11.9

12.1

12.3

12.6

11.7

11.7

11.7

11.9

12.2

12.4

12.6

75

TC

195

199

203

219

238

253

268

204

206

209

225

244

258

273

212

213

214

229

248

263

277

SHC

195

187

180

150

120

95.8

71.3

204

199

195

162

127

99.3

71.4

212

210

208

173

134

103

71.5

kW

12.1

12.2

12.2

12.5

12.7

13

13.2

12.3

12.3

12.3

12.6

12.8

13

13.3

12.4

12.4

12.4

12.6

12.9

13.1

13.3

85

TC

190

193

196

213

231

246

260

199

201

202

218

236

251

264

206

207

208

222

240

255

268

SHC

190

183

177

148

118

93.4

68.8

199

195

191

159

125

96.9

68.9

206

205

204

170

131

100

69

kW

13.5

13.5

13.6

13.8

14.1

14.4

14.6

13.6

13.7

13.7

13.9

14.2

14.5

14.7

13.7

13.8

13.8

14

14.3

14.5

14.8

95

TC

184

187

190

205

222

236

250

193

194

195

210

227

241

254

200

200

201

214

231

245

258

SHC

184

179

173

144

114

90.2

65.9

193

190

187

156

121

93.7

66.1

200

199

199

167

128

97.1

66.2

kW

15

15

15.1

15.4

15.7

15.9

16.2

15.1

15.2

15.2

15.5

15.8

16

16.3

15.3

15.3

15.3

15.5

15.8

16.1

16.3

105

TC

178

180

182

197

213

228

240

186

187

188

201

217

232

244

193

193

193

205

221

235

247

SHC

178

173

169

141

111

87.3

62.9

186

184

183

152

118

90.8

63.1

193

193

193

163

124

94.1

63.2

kW

16.6

16.7

16.7

17

17.3

17.7

17.9

16.8

16.8

16.8

17.1

17.4

17.8

18

16.9

16.9

16.9

17.2

17.5

17.8

18

115

TC

171

172

174

188

203

217

228

179

179

179

192

207

221

232

185

185

185

195

210

224

235

SHC

171

168

165

137

107

83.6

59.6

179

178

178

149

114

87.1

59.7

185

185

185

159

121

90.4

59.9

kW

18.4

18.4

18.4

18.8

19.1

19.4

19.7

18.6

18.6

18.6

18.9

19.2

19.5

19.8

18.7

18.7

18.7

19

19.3

19.6

19.9

125

TC

164

165

165

178

192

205

216

171

171

171

182

196

208

219

177

177

177

185

199

211

222

SHC

164

162

160

134

104

79.8

56.1

171

171

171

145

110

83.2

56.3

177

177

177

155

117

86.5

56.4

kW

20.2

20.3

20.3

20.6

21

21.3

21.6

20.4

20.4

20.4

20.8

21.1

21.4

21.7

20.6

20.6

20.6

20.8

21.2

21.5

21.8

581A210 (18 Tons) (cont)

Temp (F)

Air Ent

Cond

Evap Air — Cfm/BF

8100/0.08

9000/0.09

Evap Air — Ewb (F)

54

58

62

67

72

76

80

54

58

62

67

72

76

80

60

TC

227

227

228

243

262

277

293

233

233

233

246

265

280

295

SHC

227

226

224

187

144

109

75.1

233

233

233

198

151

113

75.1

kW

10.5

10.6

10.6

10.7

11

11.2

11.4

10.6

10.6

10.6

10.8

11

11.3

11.5

70

TC

222

222

222

236

255

271

284

228

228

227

239

258

272

287

SHC

222

221

221

185

142

107

72.8

228

228

227

195

148

110

72.9

kW

11.8

11.8

11.8

12

12.2

12.5

12.7

11.9

11.9

11.8

12

12.3

12.5

12.7

75

TC

219

219

219

232

251

266

280

225

224

224

235

254

268

282

SHC

219

218

218

183

140

106

71.6

225

224

224

193

147

109

71.7

kW

12.5

12.5

12.5

12.7

12.9

13.2

13.4

12.6

12.5

12.5

12.7

13

13.2

13.4

85

TC

213

213

213

225

243

258

271

218

218

218

228

245

260

273

SHC

213

213

213

180

138

103

69.1

218

218

218

190

144

107

69.2

kW

13.8

13.8

13.8

14.1

14.3

14.6

14.8

13.9

13.9

13.9

14.1

14.4

14.6

14.8

95

TC

206

206

206

217

234

248

260

211

211

211

220

236

250

262

SHC

206

206

206

177

134

100

66.3

211

211

211

187

141

103

66.4

kW

15.4

15.4

15.4

15.6

15.9

16.1

16.4

15.5

15.5

15.5

15.6

15.9

16.2

16.4

105

TC

199

199

199

208

224

238

249

203

203

204

210

226

240

251

SHC

199

199

199

173

131

97.2

63.2

203

203

204

183

137

100

63.4

kW

17

17.1

17.1

17.3

17.6

17.9

18.1

17.2

17.2

17.2

17.3

17.6

17.9

18.1

115

TC

191

191

191

198

213

226

237

195

195

195

201

215

228

238

SHC

191

191

191

169

127

93.5

60

195

195

195

179

133

96.6

60

kW

18.8

18.8

18.8

19

19.3

19.7

19.9

18.9

18.9

18.9

19.1

19.4

19.7

19.9

125

TC

182

182

182

188

201

213

224

186

186

186

190

203

215

225

SHC

182

182

182

165

123

89.6

56.5

186

186

186

174

129

92.6

56.6

kW

20.7

20.7

20.7

20.9

21.2

21.6

21.9

20.9

20.9

20.9

21

21.3

21.6

21.9

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

tldb = tedb –

sensible capacity (Btuh)

1.10 x cfm

hlwb = hewb –

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

CFM

ENTERING WET-BULB (F)

54

58

62

67

72

76

80

Bypass Factor

5400

0.424

0.238

0.125

0.120

0.138

0.000

0.000

6300

0.478

0.304

0.153

0.132

0.145

0.000

0.000

7200

0.525

0.364

0.190

0.144

0.153

0.000

0.000

8100

0.562

0.414

0.231

0.156

0.162

0.000

0.000

9000

0.594

0.456

0.281

0.168

0.170

0.000

0.000