ELECTRICAL DATA — 581A (cont)

ELECTRICAL DATA — 581A155,180

LEGEND

*Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combina-

tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage
is greater than 2%.
Use the following formula to determine the per-
cent of voltage imbalance.
% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.

UNIT
581A

NOMINAL

VOLTAGE

(3 Ph, 60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

COMBUSTION

FAN MOTOR

POWER

SUPPLY

No. 1

No. 2

Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp

FLA

FLA LRA

FLA

MCA

MOCP*

155

(Standard

IFM)

208/230

187

253

20.7

156

20.7

156

3

0.5

1.70

2.9

8.8/ 8.4

0.57

60/60

80/80

4.6

18.8

0.57

65/65

80/80

460

414

506

10.0

75

10.0

75

3

0.5

0.80

2.9

4.2

0.30

29

35

2.3

6.0

0.30

31

40

575

518

633

8.2

54

8.2

54

3

0.5

0.75

3.0

3.9

0.57

25

30

2.1

4.8

0.57

27

30

155

(Optional

IFM)

208/230

187

253

20.7

156

20.7

156

3

0.5

1.70

3.7 10.5/11.0

0.57

62/63

80/80

4.6

18.8

0.57

67/67

80/80

460

414

506

10.0

75

10.0

75

3

0.5

0.80

3.7

4.8

0.30

30

35

2.3

6.0

0.30

32

40

180

208/230

187

253

32.1

195

20.7

156

3

0.5

1.70

5.0 15.8/15.8

0.57

82/82

110/110

4.6

18.8

0.57

86/86

110/110

460

414

506

16.4

95

10.0

75

3

0.5

0.80

5.0

7.9

0.30

41

50

2.3

6.0

0.30

43

50

575

518

633

12.0

80

8.2

54

3

0.5

0.75

5.0

6.0

0.57

31

40

2.1

4.8

0.57

34

45

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

7
457