PHYSICAL DATA — 580F036-073 (cont)

LEGEND

*Evaporator coil fin material/condenser coil fin material. Contact your local repre-

sentative for details about coated fins.

†Weight of 14-in. roof curb.

**Single phase/three-phase.

††Rollout switch lockout is manually reset by interrupting power to unit or resetting

thermostat.

***Three-phase standard high heat models have heating input values as shown.

Single-phase standard high heat models have one-stage heating with heating
input values as follows:

580F036 — 115,000 Btuh
580F048,060 — 150,000 Btuh

†††California SCAQMD compliant Low NO

x

models have combustion products

that are controlled to 40 nanograms per joule or less.

NOTES:

1. High-static motor not available on single-phase units.
2. An LP kit is available as an accessory. Kit may be used at elevations as high

as 2000 ft. LP kit is not used with Low NOx units.

UNIT SIZE 580F

036

048

060

072

073

FURNACE SECTION

Rollout Switch Cutout
Temp (F)††

195

195

195

195

195

Burner Orifice Diameter
(in. ...drill size)

Natural Gas

Std

074

.113...33

.113...33

.113...33

.113...33

115

.113...33

.113...33

.113...33

.113...33

.113...33

150

.113...33

.129...30

.129...30

.129...30

.129...30

060N

.102...38

.102...38

090N

.102...38

.102...38

.102...38

120N

.102...38

.116...32

.116...32

Liquid Propane

Alt

074

.089...43

.089...43

.089...43

.089...43

115

.089...43

.089...43

.089...43

.089...43

.089...43

150

.089...43

.104...37

.104...37

.102...38

.104...37

Thermostat Heat Anticipator
Setting (amps)

208/230 v and 575 Stage 1

.14

.14

.14

.14

.14

Stage 2

.14

.14

.14

.14

.14

460 v

Stage 1

.14

.14

.14

.14

.14

Stage 2

.14

.14

.14

.14

.14

Gas Input (Btuh)

Standard Units

074

—/74,000

—/74,000

—/74,000

—/74,000

(Stage 1/Stage 2)

115

—/74,000

—/115,000

—/115,000

—/115,000

—/115,000

150***

82,000/115,000

120,000/150,000

120,000/150,000

120,000/150,000

120,000/150,000

Low NOx Units

060N†††

60,000

60,000

090N†††

60,000

90,000

90,000

120N†††

90,000

120,000

120,000

Efficiency (Steady

State) (%)

80

80

80

80

80

Temperature Rise Range

074

15-45

15-45

15-45

15-45

115

15-45

35-65

35-65

35-65

35-65

150

55-85

50-80

50-80

50-80

50-80

060N

20-50

20-50

090N

20-50

30-60

30-60

120N

30-60

40-70

40-70

Manifold Pressure (in. wg)

Natural Gas

Std

3.5

3.5

3.5

3.5

3.5

Liquid Propane

Alt

3.5

3.5

3.5

3.5

3.5

Gas Valve Quantity

1

1

1

1

1

Gas Valve Pressure Range

Psig

0.180-0.487

0.180-0.487

0.180-0.487

0.180-0.487

0.180-0.487

in. wg

5.0-13.5

5.0-13.5

5.0-13.5

5.0-13.5

5.0-13.5

Field Gas Connection
Size (in.)

1

/

2

1

/

2

1

/

2

1

/

2

1

/

2

HIGH-PRESSURE SWITCH (psig)

Standard Compressor

450 ± 50

500 ± 50

500 ± 50

Internal Relief (Differential)

Cutout

428

428

428

Reset (Auto.)

320

320

320

LOW-PRESSURE SWITCH (psig)

Cutout

7 ± 3

Reset (Auto.)

22 ± 7

FREEZE PROTECTION
THERMOSTAT (F)

Opens

30 ± 5

Closes

45 ± 5

OUTDOOR-AIR INLET SCREENS

Cleanable

Quantity...Size (in.)

Varies by Option Selected

RETURN-AIR FILTERS

Throwaway

Quantity...Size (in.)

2...16 x 25 x 2

Al

Aluminum

Bhp —

Brake Horsepower

Cu

Copper

58
0

F

03
6-

15
1

Advertising