PERFORMANCE DATA (cont)

COOLING CAPACITIES, STANDARD UNITS (cont)

Standard Ratings

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil.

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581B120 (10 TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

3000/0.03

3200/0.03

4000/0.04

5000/0.04

Air Entering Evaporator — Ewb

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

140.3

129.4

115.0

141.2

130.4

118.1

145.2

134.0

122.1

147.5

136.6

125.3

SHC

65.6

82.2

97.4

66.7

84.4

101.5

71.3

93.1

113.5

77.9

103.7

124.7

kW

7.35

7.21

7.12

7.37

7.23

7.13

7.46

7.31

7.17

7.51

7.37

7.22

85

TC

137.7

125.3

110.0

138.9

126.6

113.6

142.6

130.6

117.7

144.6

133.3

122.3

SHC

65.0

81.2

95.2

66.3

83.6

99.7

71.0

92.8

112.0

76.9

103.1

122.2

kW

8.29

8.13

8.02

8.32

8.16

8.03

8.40

8.24

8.09

8.45

8.31

8.16

95

TC

133.8

120.7

103.0

135.1

121.9

107.2

138.8

125.8

112.8

141.7

128.5

118.5

SHC

63.9

79.6

92.2

65.2

82.0

97.0

70.6

91.5

109.7

76.9

102.5

118.4

kW

9.33

9.16

8.98

9.35

9.18

9.00

9.44

9.27

9.07

9.51

9.33

9.19

105

TC

128.7

115.4

96.5

129.8

116.6

99.7

133.7

120.3

107.1

136.7

122.8

114.5

SHC

62.3

77.6

89.4

63.6

80.2

93.5

69.4

89.6

106.8

76.0

100.6

114.3

kW

10.46

10.28

10.00

10.47

10.30

10.07

10.57

10.38

10.21

10.66

10.43

10.31

115

TC

123.2

109.1

90.8

124.3

110.3

92.2

127.9

114.4

100.8

130.9

116.8

110.1

SHC

60.4

75.1

86.6

61.9

77.8

90.0

67.6

87.6

100.7

74.6

98.7

109.9

kW

11.66

11.47

11.20

11.68

11.51

11.25

11.77

11.60

11.41

11.89

11.66

11.58

125

TC

117.5

101.8

86.2

118.5

103.0

87.4

121.6

107.1

96.0

124.1

110.3

104.8

SHC

58.5

72.5

84.5

60.0

75.0

87.3

65.8

85.1

96.0

72.5

96.9

104.8

kW

12.99

12.77

12.50

13.02

12.81

12.55

13.10

12.92

12.74

13.19

13.01

12.91

581B150 (12

1

/

2

TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

3750/0.08

4300/0.09

5000/0.11

6250/0.13

Air Entering Evaporator — Ewb

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

167.1

154.3

142.0

169.8

157.7

144.8

173.5

160.6

148.4

176.5

164.5

153.3

SHC

82.5

103.5

123.6

85.8

109.7

132.0

90.3

117.7

141.9

98.2

130.7

153.1

kW

9.44

9.18

8.95

9.50

9.26

9.01

9.60

9.33

9.07

9.68

9.43

9.17

85

TC

162.3

149.3

135.6

165.1

152.5

139.5

168.8

155.3

143.5

172.1

159.2

149.3

SHC

80.9

101.4

120.9

84.4

107.9

129.9

89.6

115.8

139.8

97.6

129.3

149.1

kW

10.49

10.18

9.97

10.55

10.27

10.02

10.67

10.32

10.11

10.75

10.43

10.21

95

TC

156.5

143.7

126.3

159.6

146.8

131.3

162.3

149.8

136.5

166.5

153.2

144.5

SHC

79.1

99.5

116.5

83.0

106.1

126.0

87.6

114.2

135.8

95.8

127.7

144.4

kW

11.60

11.30

11.01

11.69

11.39

11.10

11.75

11.47

11.20

11.87

11.56

11.35

105

TC

150.0

136.2

115.7

153.0

139.3

120.9

155.6

142.5

138.5

158.8

145.9

138.8

SHC

76.5

96.7

111.2

80.8

103.5

120.0

85.7

112.3

128.4

93.6

125.9

138.7

kW

12.76

12.42

12.09

12.83

12.52

12.20

12.91

12.62

12.32

12.96

12.72

12.52

115

TC

141.8

122.2

104.4

144.3

126.1

110.8

147.7

129.4

118.9

150.7

135.2

130.1

SHC

73.6

91.2

104.2

77.9

98.5

110.8

83.4

107.3

118.4

91.8

121.9

129.9

kW

13.85

13.55

13.22

13.94

13.64

13.35

14.05

13.73

13.50

14.15

13.86

13.70

125

TC

132.5

108.6

93.9

134.8

111.4

100.7

137.6

114.4

106.6

140.3

122.9

120.1

SHC

70.9

85.7

93.8

74.8

92.9

100.7

80.2

101.4

106.5

89.0

116.3

120.1

kW

15.04

14.66

14.44

15.14

14.75

14.55

15.23

14.85

14.72

15.29

14.94

14.84

BF

Bypass Factor

Edb —

Entering Dry Bulb

Ewb —

Entering Wet Bulb

kW

Compressor Motor Power Input

SHC —

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature corresponding to enthalpy of air leaving
evaporator coil (h

lwb

)

h

lwb

=

h

ewb

total capacity (Btuh)

4.5 x cfm

581

B0

36

-15

0

Advertising