SECTION 6 - JLG CONTROL SYSTEM

6-58

– JLG Lift –

3121259

DRIVE – LOSS OF CURRENT
FEEDBACK

33410

Measured feedback current is less than 225mA while Ground Module
output is greater than 40% (Displayed on Analyzer DIAGNOSTICS
menu).

The Ground Module suspends
Drive Forward/Reverse com-
mands and reverts to Open Cur-
rent loop control for Drive; Drive
speed is limited to Creep after
both Drive Forward/Reverse
controls have been returned to
neutral and the machine is not
Enabled.

Part or all of the commanded
current is being diverted from
the ground return path. Inspect
wiring for physical damage and
check for wire continuity and a
low resistance return path.
Cycle power to clear the fault.

SWING VALVES – SHORT TO
BATTERY

33412

The Ground Module detects a short to battery at either the Swing
Right or Swing Left valve

Ground Module Swing Left and
Right outputs are disabled and
open the ground current return
path is open circuited.

Inspect wiring for physical
damage and check for wire
continuity. Cycle power to clear
the fault.

TOWER LIFT – CURRENT FEED-
BACK READING TOO LOW

33413

The Ground Module calls for current greater than 250mA, but the
actual current is at least 125mA less than the called for current for
more than 1 second

The Ground Module suspends
Tower Lift commands and
reverts to Open Current loop
control for Tower Lift; Tower Lift
speed is limited to Creep after
both Tower Lift Up/Down con-
trols have been returned to
neutral and the machine is not
Enabled.

Part of the commanded current
is being divided either prior to
the solenoid connection or on
the ground return path. Inspect
wiring for physical damage and
check for wire continuity and a
low resistance return path.
Cycle power to clear the fault.

SWING – CURRENT FEEDBACK
READING TOO LOW

33414

The Ground Module calls for current greater than 250mA, but the
actual current is at least 125mA less than the called for current for
more than 1 second

The Ground Module suspends
Swing Left/Right commands
and reverts to Open Loop Cur-
rent control for Swing; Swing
speed is limited to Creep after
both Swing Left/Right have
been returned to neutral and
the machine is not Enabled

Part of the commanded current
is being divided either prior to
the solenoid connection or on
the ground return path. Inspect
wiring for physical damage and
check for wire continuity and a
low resistance return path.
Cycle power to clear the fault.

FLOW CONTROL VALVE – CUR-
RENT FEEDBACK READING TOO
LOW

33415

The Ground Module calls for current greater than 250mA, but the
actual current is at least 125mA less than the called for current for
more than 1 second

The Ground Module suspends
and reverts to Open Current
loop control for Flow Control
Valve; Tele In/Out, Jib Up,
Rotate Right/Left, and Level
Up/Down speed is limited to
Creep after controls for those
functions have all been simul-
taneously returned to neutral
and the machine is not Enabled

Part of the commanded current
is being divided either prior to
the solenoid connection or on
the ground return path. Inspect
wiring for physical damage and
check for wire continuity and a
low resistance return path.
Cycle power to clear the fault.

TOWER LIFT – CURRENT FEED-
BACK READING LOST

33416

Measured feedback current is less than 225mA while Ground Module
output is greater than 40% (Displayed on Analyzer DIAGNOSTICS
menu).

The Ground Module suspends
commands and reverts to Open
Current loop control for Tower
Lift; Tower Lift speed is limited
to Creep after both Lift Up/
Down controls have been
returned to neutral and the
machine is not Enabled.

Part or all of the commanded
current is being diverted from
the ground return path. Inspect
wiring for physical damage and
check for wire continuity and a
low resistance return path.
Cycle power to clear the fault.

Table 6-10. Fault Code Troubleshooting Information

Help Message

DTC

Condition Producing DTC

Control System Response or

Machine Condition

Corrective Action/

Operational Requirement

for Function Movement

and/or to Clear Fault