3 modbus registers, 1 modbus input registers, Modbus registers -1 – CiDRA Passive Sonar Transmitters User Manual

Page 15: Modbus input registers -1, Table 4, Modbus registers

Advertising
background image

3

MODBUS REGISTERS

3.1 Modbus

Input

Registers

Note: Float values may be set to QNAN if transmitter is not configured to generate those values. (QNAN
means ‘Quiet Not A Number’, a computing term for an IEEE floating point representation for the result of
a numerical operation which cannot return a valid number value.)

Table 4

Modbus Input Registers

Address Size

Type Value

Description

Notes

1 2

Float

Flow Rate as
Displayed

Flow Rate as it appears on the LCD.

Will be set to QNAN when not
displayed.

3

2

Float

Total Flow

Total Flow.

5

2

Float

VF Quality

Measured flow quality.

7

2

Float

Flow Rate

Measured flow rate in ft/s without any filtering applied.

As reported by DSP.

9

2

Float

GVF as Displayed

GVF as it appears on the LCD.

Will be set to QNAN when not
displayed.

11 2

re

Float

Pressu

Pressure as used in calculation of GVF in configured
units.

13 2

Float

Temperature

Temperature as used in calculation of GVF in
configured units.

15

2

Float

SOS as Displayed

SOS as it appears on the LCD.

Will be set to QNAN when not
displayed.

17

2

Float

SOS Quality

Measured SOS quality.

19

2

Float

SOS

Measured SOS in ft/s without any filtering applied.

As reported by DSP.

21 2

Float

SOS Flow Rate as
Displayed

SOS Flow Rate as it appears on the LCD.

Will be set to QNAN when not
displayed.

23 2

Float

SOS Flow Rate
Quality

Measured SOS flow quality.

25

2

Float

TLF as Displayed

TLF as it appears on the LCD.

Will be set to QNAN when not
displayed.

27

2

Float

Total TLF

Measured total TLF.

29

2

Float

TLF

Measured TLF in ft/s without any filtering applied.

31 2

Float

Band

Temperature

Temperature measured by the sensor band.

20959-01 Rev 02

Page 3-1