Table 5 Modbus Holding Registers (continued)

Address Size

Type Value

Description

Values

1521 2

Float

SOS_QUALITY_DEL
TA

Delta change from SOS minimum quality at minimum
SOS (SOS_MIN_QUALITY) to minimum quality at max
SOS (SOS_MIN_QUALITY+ SOS_QUALITY_DELTA).

1523 2

Float

YELLOW_QUALITY
_PERCENT

Percentage of VF quality or SOS quality (depending on
op mode) below which the display will indicate a 3 level
of 'YEL', if configured to display 3 level quality.

1525 2

Float

TOTAL_LOW_CUT

Define low limit of totalizer. Input as % of flow rate.
Readings below this value will not be totalized.

1527

2

Float

REYNOLDSC0

Volumetric flow calibration coefficient C0.

1529

2

Float

REYNOLDSC1

Volumetric flow calibration coefficient C1.

1531

2

Float

REYNOLDSC2

Volumetric flow calibration coefficient C2.

1533 2

Float

TLF_SENSOR_INP
UT_SCALE_1

Sets multiplier used to scale the 4-20mA input Sensor 1.

1535 2

Float

TLF_SENSOR_INP
UT_SCALE_2

Sets multiplier used to scale the 4-20mA input Sensor 2.

1537 2

Float

TLF_SENSOR_INP
UT_OFFSET_1

Sets offset used to calculate the 4-20mA input Sensor 1
value.

1539 2

Float

TLF_SENSOR_INP
UT_OFFSET_2

Sets offset used to calculate the 4-20mA input Sensor 2
value.

1541 2

Float

PRIMARY_420_HIG
H_END

Define high (20mA) end of primary 4-20mA output.

1543 2

Float

PRIMARY_420_LO
W_END

Define low (4mA) end of primary 4-20mA output.

1545 2

Float

PRIMARY_420_SCA
LE

Multiplier applied to primary 4-20mA output for
calibration purposes

1547 2

Float

PRIMARY_420_OFF
SET

Constant offset applied to primary 4-20mA output for
calibration purposes.

1549 2

Float

SECONDARY_420_
HIGH_END

Define high (20mA) end of primary 4-20mA output.

1551 2

Float

SECONDARY_420_
LOW_END

Define low (4mA) end of primary 4-20mA output.

1553 2

Float

SECONDARY_420_
SCALE

Multiplier applied to primary 4-20mA output for
calibration purposes.

20959-01 Rev 02

Page 3-11