CiDRA Passive Sonar Transmitters User Manual

Page 43

Advertising
background image

9-01 Rev 02

Page 3-28

Table 5 Modbus Holding Registers (continued)

Address Size

Type Value

Description

Values

4563 2

Long

AGC_PERCENT_TH
RESHOLD_LOW

Represents the percentage value of Low Threshold
faults required to be detected before asserting an
Insufficient Gain condition during AGC functions.

4565 2

Long

AGC_SAMPLE_WIN
DOW

Represents the time window in seconds during which
AGC High and Low Threshold faults will be counted.
This is a sliding time window when used during Auto
Gain Adjust functions and a One-Shot time window
during Gain Test functions.

4567 2

Long

AGC_RUN_MODE

For future use only. This parameter will be used to
specify if the AGC functions should be executed in a
Continuous mode, or in Single Execution mode.

5001

2

Float

Pressure Input

External pressure measurement input.

No write control required on these
inputs, just write to them.

5003

2

Float

Temperature Input

External temperature measurement input.

No write control required on these
inputs, just write to them.

5005

2

Float

External Input 1

External Input 1.

No write control required on these
inputs, just write to them.

5007

2

Float

External Input 2

External Input 2.

No write control required on these
inputs, just write to them.

5009

2

Float

External Input 3

External Input 3.

No write control required on these
inputs, just write to them.

5501 32

Short

Softing Firmware
Rev

Firmware revision of the Softing board.

5533

32

Short

PD Tag

Fieldbus PD Tag.

5565

32

Short

Device ID

Fieldbus Device ID.

5597

1

Short

Node Address

Fieldbus Node Address.

5598

1

Short

RB Block Mode

Fieldbus Resource Block Mode.

5599

1

Short

TB Block Mode

Fieldbus Transducer Block Mode.

2095