3.14.3. How to Use the Charts

The power dissipation in the chart includes the losses of the rectifying bridge.
Regarding Figure 37 and Figure 38, the following should be noted:

DC Bus Voltage (VDC)

Rectified Voltage (VAC)

560

3X400

680

3X480

330

3X230

The charts above are based upon theoretical worst-case conditions. Actual test results show
30% to 50% better power dissipation.
To determine if your application needs a heat sink:

1.

Allow maximum heat sink temperature to be 80 °C or less (shunt down is 6 °C to 8 °C
higher).

2.

Determine the ambient operating temperature of the Trombone as ≤ 40 °C.

3.

Calculate the allowable temperature increase according to the following example: For
an ambient temperature of 40 °C, ΔT = 80 to 40°C = 40°C

4.

Use the chart to find the actual dissipation power of the drive. Follow the voltage curve
to the desired output current and then find the dissipated power.