Step 2: Power and Motor Connection

Table 5: Connecting the Main Power and Motor Cables

3.4.2.1.

Connecting the Motor Cable

Connect the motor power cable to the M1, M2, and M3 terminals of the main power connector
and the fourth wire to the PE (Protective Earth) on the heat sink (see diagram above). The phase
connection order is arbitrary because the Composer will establish the proper commutation
automatically during setup.

Notes for connecting the motor cables:

For best immunity, it is highly recommended to use a shielded (not twisted) cable for the

motor connection. A 4-wire shielded cable should be used. The gauge is determined by the
actual current consumption of the motor.

Connect the shield of the cable to the closest ground connection at the motor end.

Connect the shield of the cable to the PE terminal on the Eagle.

Be sure that the motor chassis is properly grounded.

To close the motor cable into the drive, use the barrel connector, M6 spring washer and M6

nut (in the drive). The required torque is 3 to 4 Nm.

To close the PE wire into the drive, use the barrel connector, M5 flat washer, M5 spring washer

and M5 screw to the heat sink. The required torque is 3 to 4 Nm.

M6 nut (available with

the drive)

M6 spring

washer

Barrel

connector